Part A System installation and start-up Sect. 2.2

05/2003

IFC 110 F

17

2.2

Current output I


• The current output is electrically isolated from all other circuits.


Setting data and functions can note down in the Table in Sect. 3.

Please also refer to Section 2.7 ”Standard factory settings”.


All operating data and functions are adjustable (see Sections 4.4 and 5.6, Fct. 1.05).


Max. load :

active operation 15-500

passive operation

≤ 800 Ω


Selfcheck : - interrupting the mA loop, and

- short-circuit of mA loop via test function, see Fct. 2.03

or when power supply is switched on in Fct. 3.07

Error message on display (see Fct. 1.04, Section 5.4) and/or

status output (see Fct. 1.07-1.10, Section 5.8).


Current value for error identification is adjustable, see Fct. 1.05 and Section 5.6.


Range change-over, automatically or externally by control input,

see Sections 4.4 and 5.19, Fct. 1.07-1.10 and 1.11-12.

Setting range from 5-80% of Q

100%

(corresponding low to high range ratio from 1:20 to 1:1.25).

Change-over from high to low range at approx. 85% of low range and vice versa at approx.

98% of low range.

The active range is signalled via one of the four status outputs.

Forward/reverse flow measurement (F/R mode) is possible (see Section 5.15).


Connection diagrams see Section 2.6.