Change procedure b, Fct. 1.02 timeconst. change setting to 3 seconds, Set here (fct. 3.02, subfunction ”full scale”) – KROHNE IFC 110 Converter User Manual

Page 63: Example: full-scale range q, Set amplitude to e.g. ± 2, 2% % ∆t s, T 3 s = 0.66 s

Advertising
background image

Part C Special applications, functional checks, service, and order numbers Sect. 6.6

05/2003

IFC 110 F

63

Change procedure B

PLEASE NOTE:
Do not proceed according to change procedure B unless the steps of change procedure A
proved unsuccessful.

Change procedure B must not be adopted for pulsating flows downstream of positive
displacement pumps.

The following settings result in a modified dynamic behaviour of the system which is no longer
defined by the setting of the time constant in Fct. 1.02.

• Fct. 1.02 TIMECONST.

Change setting to 3 seconds.

• Fct. 3.06 APPLICAT.

– Select ”YES” in subfunction ”SPEC. FILT.” to activate a special noise filter.

– Subfunction ”LIMIT VAL.” defines a window with a width (somewhere around the mean
flow) equivalent to the value in PERCENT of the full-scale range Q

100%

set here

(Fct. 3.02, subfunction ”FULL SCALE”).

This value must always be a lot smaller than the amplitude of the display ripple

(peak-to-peak).

Example:

full-scale range Q

100%

500

m³/h

ripple mean value

± 25 m³/h = ± 5% of full-scale range Q

100%

set amplitude to e.g.

± 2%

Signals outside the ± LIMIT VALUE window are cut off (clipping). When e.g. interferences

cause the measuring value to leave this window for a short time, the rate of change of the
display and outputs is limited to...

∆Q

max

%

LIMIT VAL.

Formula applying to

∆Q

max

2% %

∆T s

=

TIMECONST. (Fct. 1.02)

the above example

∆T

3 s

= 0.66

s

=

The delay required for passing on major changes of flow to the display and outputs is defined in
subfunction ”LIMIT CNT.”.

Set subfunction ”LIMIT CNT.” to 10 on a trial basis.

Should the measuring value leave the above window in one direction more than 10 times, this
window is temporarily rendered inactive.

Display and outputs follow major changes of flow with the appropriate speed.

This setting provides an additional dead time for display and outputs:

Dead time = LIMIT CNT. x duration of measuring cycle
Duration of measuring cycle = approx. 60 ms (for magnetic field frequency = 1/6 ´ line frequency,

see Section 3.02, subfunction ”FIELD FREQ.”).

A ”10” set in subfunction ”LIMIT CNT.” results in a dead time of approx. 600 milliseconds.

By changing the subfunctions ”LIMIT VAL.”, ”LIMIT CNT.” and ”TIMECONST.”

(Fct. 1.02) on a trial basis, a setting can normally be found which ensures

that the display and outputs are sufficiently stable.

Each of the steps described above must be followed by a check

of the ripple of display and outputs in measuring mode.