Part C Special applications, functional checks, service, and order numbers Sect. 6.4

05/2003

IFC 110 F

59


Electrical connection

HART

®

- active

not with multidrop operation

HART

®

- passive

only with multidrop operation


Power supply unit (and section switch amplifier) must be set up accordingly if in use for HART

®

operation. For setting active/passive operation see Sect. 6.8.


Settings and operation

Fct.

Parameter

Point-to-point mode

Multidrop mode

1.05 Function

1 CORRECT. or 2 CORRECT.

OFF

Range I

4-20 mA or I

0%

≥ 4 mA

I

0%

≥ 4 mA

3.09 Communication HART HART

Address

0

01, 02, 03 ..... 15

(use one address at

one time only)

Operation
Current output


active or passive


passive only


For further information on setting the signal converter refer to chapters 4 and 5.


HART

®

operating tools / Device Description (DD)


The signal converter can be operated either via its local operator interface or by means of the
HART

®

communicator, which is available from KROHNE.


Operator control by means of the HART

®

communicator requires a device description (DD) which

we can load for you into the communicator. We can, of course, also load the DDs of all
manufacturers who have filed their DDs with the HART

®

Communication Foundation.


If you wish to use the signal converter in your operating tool, for example, please ask for the
description of the HART

®

command used so that you can address the complete signal converter

functionality via HART

®

.

active




to HART

®

- communicator

or smart-converter

passive

to next
HART

®

- device




power supply unit



to HART

®

- communicator

or Smart- converter

Bürde

≥ 230 Ω