Part B IFC 110 F Signal converter Sect. 5.6

05/2003

IFC 110 F

43

5.6

Internal power supply (E+/E-) for connected loads

Passive loads connected to the outputs and inputs can be fed by means of the internal power
supply (terminals E+/E-).

U

=

24 V DC (observe polarity)

Ri = approx. 15 Ω

I

≤ 100 mA

Connection diagrams, see Section 2.6.

5.7

Current output I

Fct. 1.05 CUR. OUTP. I
Press

key

FUNCT. I = select function for current output, presskey

OFF

(switched off, no function)

+ DIR.

(measurement in one direction, refer to selection of main flow direction in

– DIR.

Fct. 3.02 FLOW METER, subfunction ”FLOW DIR.”)

2 DIR.

}

(2 flow directions, F/R mode, forward/reverse)

Select with

and keys.

Press

key to change to subfunction ”RANGE I”.

Exception:

when ”OFF” is selected, return to Fct. 1.05 CUR. OUTP. I.

When ”2 DIR.” is selected, change to subfunction ”REV. RANGE”.

REV. RANGE = select full-scale range for reverse flow

(only displayed when ”2 DIR.” is selected in ”FUNCT. I” above)
Press

key

100 PCT.

(same full-scale range Q

100%

as forward flow, see Fct. 1.01)

PERCENT (adjustable range) Setting range 005 - 150 % of Q

100%

(see Fct. 1.01)

Select with

and keys.

Press

key to change to numerical setting.

Change flashing number (cursor) with keys

and ↓. Useandkeys to shift cursor 1 place

to right or left.
Flashing numbers (cursor) can also be directly set with the 10-key keyboard.
Press

key to change to subfunction ”RANGE I”.

RANGE I = select the measuring range, press key

0 - 20 mA

4 - 20 mA

}

fixed ranges

mA (any value)

I

0%

– I

100%

(value

I

0%

< I

100%

!) 0-16 mA 4-20 mA

Press

key to change to numerical setting.

Select with

and keys.

Change flashing number (cursor) with keys

and ↓ . Useandkeys to shift cursor

1 place to right or left.
Flashing numbers (cursor) can also be directly set with the 10-key keyboard.
Press

key to change to subfunction ”I ERROR”