Part C Special applications, functional checks, service, and order numbers Sect. 6.5

05/2003

IFC 110 F

61

6.5 Pulsating

flow


Application
Downstream of positive displacement pumps (reciprocating or diaphragm pumps) without
pulsation damper.

Resetting the signal converter, see Sections 4 and 5.

Changing the settings
• Fct. 3.02 FIELD FREQ. (change the magnetic field frequency)

– Stroke frequency less than 80 strokes/min. (at max. pump lift), do not change setting.

– Stroke frequency 80-200 strokes/min. (at max. pump lift), change setting to 1/2,
only recommended for PROFIFLUX 5000 F (DN 2.5-100 and

1

/

10

”-4”)

and ALTOFLUX 4000 F (DN 10, 15, 50-100 and

1

/

10

”,

1

/

2

”, 2”-4”),

for other types and sizes please consult factory.

– Please note: at stroke frequencies near the limit of 80 strokes/min. additional measurement
deviations of ± 0.5 % of the measuring value may occur occasionally.

• Fct. 3.06 APPLICAT. (adapt modulation limit of A/D converter to the application)

Change setting of subfunction ”FLOW” to ”PULSATING”.

• Fct. 1.04 DISP. FLOW (change display of flow)

Change setting to ”BARGRAPH” in order to be able to evaluate the display ripple.

• Fct. 1.02 TIMECONST. (change time constant)

– Change setting to ”ALL” and set time (t) to seconds.

1000

– Recommendation: t [s] =

min. number of strokes/min.


– Example:

min. number of strokes during operation = 50 strokes/min.


1000

t [s] =

50/min.

= 20 s

With this setting, the residual ripple of the display is approx. ± 2 % of the
measuring value. Doubling the time constant reduces the residual ripple of
the display by a factor of 2.