KROHNE IFC 110 Converter User Manual

Page 79

Advertising
background image

Part C Special applications, functional checks, service, and order numbers Sect. 7.7

05/2003

IFC 110 F

79


Example

Full-scale range

Q

100%

= 200 m³/h (Fct. 1.01)

Meter size

DN

= 80 mm = 3 inch (Fct. 3.02)

Current at

Q

0%

I

0%

= 4 mA

Q

100%

I

100%

= 20 mA

}

(Fct. 1.05)

Pulses at

Q

100%

P

100%

= 200 pulses/h (Fct. 1.06)

Flow sensor constant

GK

= 3.571 (see instrument nameplate)

Constant

(V in

m³)

(t in

h)

K

= 7074 (see table)

(DN in

mm)


Calculation of ”X” and setting of ”Y”

Q

100%

x K

200 x 7074

X =

GK x DN

2

=

3.571 x 80 x 80

= 61.905


Y = 80, setting of switch Y, see GS 8 A front panel
(comes closest to the value of X and is smaller than X).

Calculation of setpoint readings I and f

Y 40

I = I

0%

+

X

(I

100%

- I

0%

) = 4 mA +

61.905

(20mA - 4mA) = 14.3mA


Deviations are permissible between 14.1 and 14.6 mA (equivalent to ± 1.5 %).

Y 40

f =

X

x P

100%

=

61.905

x pulses / h = 180.9 pulses/h


Deviations are permissible between 178.2 and 183.6 pulses/h (equivalent to ± 1.5 %).

If you need to return your flowmeter to KROHNE,

please refer to the last-but-one page of these instructions.

Advertising