Specifications

59305, Issue 7

– March 2014

Control Specifications

Automatic Tuning Types:

Pre-Tune, Self-Tune.

Proportional Bands:

0 (ON/OFF control), 0.5% to 999.9% of input span at 0.1%
increments. ON/OFF control not valid for VMD controllers.

Automatic Reset
(Integral Time Constant):

1s to 99min 59s and OFF.

Rate
(Derivative Time Constant):

0 (OFF) to 99 min 59 s.

Manual Reset
(Bias):

Added each control algorithm execution. Adjustable in the
range 0 to 100% of output power (single output) or -100% to
+100% of output power (dual output).
Not valid for VMD controllers.

Deadband/Overlap:

-20% to +20% of Proportional Band 1 + Proportional Band 2.
Not valid for VMD controllers

ON/OFF Differential:

0.1% to 10.0% of input span.

Motor Travel Time

5 seconds to 5 minutes

Minimum Motor On Time

0.0 seconds to (Motor Travel Time/10)

Auto/Manual Control:

User-

selectable with “bumpless” transfer into and out of

Manual Control.

Cycle Times:

Selectable from 0.5s to 512 seconds in binary steps.

Setpoint Range:

Limited by Setpoint Upper Limit and Setpoint Lower Limit.

Setpoint Maximum:

Limited by Setpoint and Scale Range Upper Limit.

Setpoint Minimum:

Limited by Scale Range Lower Limit and Setpoint.

Setpoint Ramp:

Ramp rate selectable 1 to 9999 LSD’s per hour and infinite.
Number displayed is decimal-point-aligned with display.

Process Alarms

Maximum Number of Alarms
(Controllers
):

Two “soft” process alarms (high, low, deviation or band) plus
Loop Alarm.

Maximum Number of Alarms
(Indicators
):

Five “soft” alarms (process high or low)

Combinatorial Alarms:

Logical OR or AND of alarms to any suitable output.

Digital Communications

Type:

Asynchronous Serial.

Protocols Supported:

Modbus RTU (all models) and ASCII (some models).

Physical Layer:

RS485.

Zone address range:

1 to 99 (ASCII), 1 to 255 (Modbus).

Bit rate:

1200, 2400, 4800, 9600 and 19200 bps.

Bits per character:

ASCII: 10
Modbus: 10 or 11 (depending on parity setting)

Stop bits:

1

Parity:

ASCII: Even (fixed).
Modbus: None, even or odd (selectable).

Isolation:

Reinforced safety isolation from inputs and outputs.