P6100, P8100 & P4100 Model Group

Page 51

Table 12. P6100, P8100 & P4100 Set Up Mode Parameters

Parameter

Lower

Display

Upper Display

Adjustment Range

Default

Value

When
Visible

Input Filter Time
constant



OFF, 0.5 to 100.0 secs in
0.5 sec increments

.



Always

Process Variable Offset



Span of controller



Always

Primary Power



The current Primary
Output Power. Read Only.

N/A

Always

Secondary Power



The current Secondary
Output power. Read Only.

N/A



=



Primary Output
Proportional Band



0.0% (ON/OFF control)
and 0.5% to 999.9% of
input span.



.



Always

Secondary Output
Proportional Band



0.0% (ON/OFF control)
and 0.5% to 999.9% of
input span.



.

 

=



Automatic Reset
(Integral Time
Constant)



0.01 to 99.59 (1 sec to 99
mins 59 secs) and OFF

.

 

is not

.

Rate (Derivative Time
Constant)



0.00 to 99.59 (OFF to 99
mins 59 secs)

.

 

is not

.

Overlap/Deadband



-20% to +20% of the sum
of the Primary and
Secondary Proportional
Bands





is not

.

Manual Reset (Bias)



0% to 100% (-100% to

100% if



=



)





is not

.

Primary Output
ON/OFF Differential



0.1% to 10.0% of input
span (enter in % span)

.





=

.

Secondary Output
ON/OFF Differential



0.1% to 10.0% of input
span (enter in % span)

.





=

.

Primary and Secondary
Output ON/OFF
Differential



0.1% to 10.0% of input
span (enter in % span)

.





and



=

.

Setpoint Upper Limit



Current Setpoint value to
Scale Range Maximum

Range

Max.

Always

Setpoint Lower limit



Scale Range Minimum to
current Setpoint value

Range Min Always

Primary (Heat) Output
Upper Power Limit



0% to 100% of full power





is not

.

Output 1
Cycle Time



0.5, 1, 2, 4, 8, 16, 32, 64,
128, 256 or 512 secs.
Not applicable to linear
outputs





=



or





or

