P6100, p8100 & p4100 controllers, Communications parameters, Bit parameters – West Control Solutions 8700+ User Manual

Page 63: Word parameters

Advertising
background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual


Page 58

P6100, P8100 & P4100 Model Group

59305, Issue 7

– March 2014

P6100, P8100 & P4100 Controllers

–Communications Parameters

The Modbus parameter addresses, and the possible ASCII message types and parameter
indents for the P6100, P8100 & P4100 are detailed below. RO indicates a parameter is read
only, R/W indicates it can also be written to. Communications writes will not implemented if
the Communications Write Parameter is disabled. Refer to the Modbus and ASCII
Communications sections of this manual for details of the protocols used.

Bit Parameters

Bit parameters are not applicable to the ASCII protocol.

Table 14. P6100, P8100 & P4100 Communications - Bit Parameters

Parameter

Modbus

Parameter No.

Notes

Communication
Write Status

1

RO

1 = Write Enabled, 0 = Write Disabled. A negative
acknowledgement (exception code 3) is sent to write
commands if communications writes are disabled

Auto / Manual

2

R/W

1 = Manual Control, 0 = Automatic Control

Self Tune

3

R/W

1 = Activate(d), 0 = Dis-engage(d)

Pre tune

4

R/W

1 = Activate(d), 0 = Dis-engage(d)

Alarm 1 Status

5

RO

1 = Active, 0 = Inactive

Alarm 2 Status

6

RO

1 = Active, 0 = Inactive

Setpoint Ramping

7

R/W

1 = Enable(d), 0 = Disable(d)

Loop Alarm Status

10

R/W

1 = Active/Enable, 0 = Inactive/Disable

Loop Alarm

12

R/W

Read to get loop alarm status. Write 0/1 to
disable/enable.

Digital Input 2

13

RO

State of Option B digital input.

To set the bit value to 1 write FF, to set the bit value to 0 write 00. Refer to Function Code 05 in the
Modbus Communications section.

Word Parameters

Table 15. P6100, P8100 & P4100 Communications - Word Parameters

Parameter

Modbus

Parameter No.

ASCII Ident &

Message Types

Notes

Process Variable

1

RO

M

Type 2

RO

Current value of PV.

If under-range = 62976 (<??>5 ASCII)

If over-range = 63232 (<??>0 ASCII)

If Sensor break = 63488 (ASCII = n/a)

Setpoint

2

R/W

S

Type 2

Type 3/4

RO

R/W

Value of currently selected setpoint.
(Target setpoint if ramping).
Parameter is read only if the current
setpoint is RSP.

Output Power

3

R/W

W

Type 2

Type 3/4

RO

R/W

0% to 100% for single output;

100%

to +100% for dual output control.
Read Only if not in manual control.

Deviation

4

RO

V

Type 2

RO

Difference between Process Variable
and Setpoint (value = PV-SP)

Advertising
This manual is related to the following products: