Specifications

Page 167

Reference Conditions

Ambient Temperature:

20

C ±2

C.

Relative Humidity:

60 to 70%.

Supply Voltage:

100 to 240V AC 50Hz ±1%.

Source Resistance:

<10Ω for thermocouple input.

Lead Resistance:

<0.1Ω/lead balanced (Pt100).

Operating Conditions

Ambient Temperature (operating):

0

C to 55

C.

Ambient Temperature (storage):

-20

C to 80

C.

Relative Humidity:

20% to 95% non-condensing.

Altitude:

Up to 2000m above sea level.

Supply Voltage:

Either 100 to 240V ±10% AC 50/60Hz
or 20 to 48V AC 50/60Hz & 22 to 55V DC

Power Consumption:

5W / 7.5 VA maximum.

Source Resistance:

1000Ω maximum (thermocouple).

PT100 Input Lead Resistance:

50Ω per lead maximum, balanced

Standards

Conformance Norms:

CE, UL, ULC, CSA

EMI standards:

Complies with EN61326 (Susceptibility & Emissions).

Safety Standards:

Complies with EN61010-1, UL61010-1 & CSA 22.2 No
1010.192 Pollution Degree 2, Installation Category II.
Also FM 3545, 1998 for Limit Controllers.

Panel Sealing:

Front to IP66 when correctly mounted

– refer to

installation section.
Rear of panel to IP20.

SUPPLEMENTARY INFORMATION FOR CSA

Compliance shall not be impaired when fitted to the final installation.

Designed to offer a minimum of Basic Insulation only. -The body responsible for the installation

is to ensure that supplementary insulation suitable for Installation Category II is achieved when
fully installed. -To avoid possible hazards, accessible conductive parts of the final installation
should be protectively earthed in accordance with EN6010 for Class 1 Equipment.

Output wiring should be within a Protectively Earthed cabinet.

Sensor sheaths should be bonded to protective earth or not be accessible.

Live parts should not be accessible without the use of a tool.

When fitted to the final installation, an IEC/CSA APPROVED disconnecting device should be

used to disconnect both LINE and NEUTRAL conductors simultaneously

A clear instruction shall be provided not to position the equipment so that it is difficult to operate