Universal input connections - thermocouple (t/c), Universal input connections, Pt100 (rtd) input – West Control Solutions 8700+ User Manual

Page 31

Advertising
background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual


Page 26

Connections

59305, Issue 7

– March 2014

Universal Input Connections - Thermocouple (T/C)

Use only the correct thermocouple wire or compensating cable from the probe to the
instrument terminals avoiding joints in the cable if possible. Failure to use the correct wire
type will lead to inaccurate readings. Ensure correct polarity of the wires by cross-
referencing the colours with a thermocouple reference table.

1

/

16

DIN

1

/

4

DIN &

1

/

8

DIN

Figure 15.

Thermocouple Input Connections

Universal Input Connections

– PT100 (RTD) input

For three wire RTDs, connect the resistive leg and the common legs of the RTD as
illustrated. For a two wire RTD a wire link should be used in place of the third wire (shown by
dotted line). Two wire RTDs should only be used when the leads are less than 3 metres long.
Avoid cable joints.

1

/

16

DIN

1

/

4

DIN &

1

/

8

DIN

Figure 16.

RTD Input Connections

Four wire RTDs can be used, provided that the fourth wire is left unconnected. This wire
should be cut short or tied back so that it cannot contact any of the terminals on the rear of
the instrument.

RTD

RTD

4

5

6

3

2

1

3

2

+

_

4

5

+

_

Advertising