West Control Solutions 8700+ User Manual

Page 90

Advertising
background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual


59305, Issue 7

– March 2014

P6700, P8700& P4700 Model Group

Page 85

Parameter

Lower
Display

Upper
Display

Description

Default
Value

When
Visible

Input type and
Range
(Continued)



N type: 0 to 1399 ºC



for Europe



for USA

Always



N type: 32 to 2551 ºF



R type: 0 to 1759 ºC



R type: 32 to 3198 ºF



S type: 0 to 1762 ºC



S type: 32 to 3204 ºF



T type: -240 to 400 ºC



T type: -400 to 752 ºF

 

T type: -128.8 to 400.0 ºC
with decimal point

 

T type: -199.9 to 752.0 ºF
with decimal point



PtRh20% vs PtRh40%:
0 to 1850 ºC



PtRh20% vs PtRh40%:
32 to 3362 ºF



Pt100: -199 to 800 ºC



Pt100: -328 to 1472 ºF

 

Pt100: -128.8 to 537.7 ºC
with decimal point

 

Pt100: -199.9 to 999.9 ºF
with decimal point



0 to 20mA DC



4 to 20mA DC



0 to 50mV DC

 

10 to 50mV DC



0 to 5V DC



1 to 5V DC



0 to 10V DC



2 to 10V DC

Scale Range
Upper Limit



Scale Range Lower Limit +100 to Range
Max

Linear
inputs =
1000
(°C/°F =
max
range)

Always

Scale Range
Lower Limit



Range Min. to Scale range Upper Limit -
100

Linear = 0
(°C/°F =
min range)

Always

Advertising
This manual is related to the following products: