West Control Solutions 8700+ User Manual

Page 70

Advertising
background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual


59305, Issue 7

– March 2014

P6170, P8170 & P4170 Model Group

Page 65

Table 16. P6170, P8170 & P4170 Configuration Mode Parameters

Parameter

Lower
Display

Upper
Display

Description

Default

Value

When
Visible

Input type and
Range





B type: 100 to 1824 ºC



for Europe



for USA

Always



B type: 211 to 3315 ºF



C type: 0 to 2320 ºC



C type: 32 to 4208 ºF



J type: -200 to 1200 ºC



J type: -328 to 2192 ºF

 

J type: -128.8 to 537.7 ºC
with decimal point

 

J type: -199.9 to 999.9 ºF
with decimal point

K type: -240 to 1373 ºC

K type: -400 to 2503 ºF

K type: -128.8 to 537.7 ºC
with decimal point

K type: -199.9 to 999.9 ºF
with decimal point



L type: 0 to 762 ºC



L type: 32 to 1403 ºF

 

L type: 0.0 to 537.7 ºC
with decimal point

 

L type: 32.0 to 999.9 ºF
with decimal point



N type: 0 to 1399 ºC



N type: 32 to 2551 ºF



R type: 0 to 1759 ºC



R type: 32 to 3198 ºF



S type: 0 to 1762 ºC



S type: 32 to 3204 ºF



T type: -240 to 400 ºC



T type: -400 to 752 ºF

 

T type: -128.8 to 400.0 ºC
with decimal point

 

T type: -199.9 to 752.0 ºF
with decimal point



PtRh20% vs PtRh40%:
0 to 1850 ºC



PtRh20% vs PtRh40%:
32 to 3362 ºF

Advertising
This manual is related to the following products: