Option slot 2 - relay output module, Option slot 2 - ssr driver output module, Option slot 2 - triac output module – West Control Solutions 8700+ User Manual

Page 34: Po2-c50, Ssr driver, Po2-c80, Triac

Advertising
background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual


59305, Issue 7

– March 2014

Connections

Page 29

Option Slot 2 - Relay Output Module

If option slot 2 is fitted with a relay output module, make connections as illustrated. The relay
contacts are rated at 2 amps resistive, 240 VAC (120V max for direct Valve Motor control).

1

/

16

DIN

1

/

4

DIN &

1

/

8

DIN

Figure 22.

Option Slot 2 - Relay Module

Option Slot 2 - SSR Driver Output Module

If option slot 2 is fitted with an SSR driver output module, make connections as illustrated.
The solid-state relay driver is a 0-10V DC signal, load resistance must be no less than 500
ohms. SSR driver outputs are not isolated from the signal input or other SSR driver outputs.

1

/

16

DIN

1

/

4

DIN &

1

/

8

DIN

Figure 23.

Option Slot 2 - SSR Driver Module

Option Slot 2 - Triac Output Module

If option slot 2 is fitted with a Triac output module, make connections as shown. This output
is rated at 0.01 to 1 amp @ 280V AC 50/60Hz. (140V max for direct Valve Motor control).

1

/

16

DIN

1

/

4

DIN &

1

/

8

DIN

Figure 24.

Option Slot 2 - Triac Module

WARNING:

THIS MODULE MUST NOT BE FITTED INTO OPTION SLOT 3.

22

23

N/C

COM

24

N/O

13

14

N/O

COM

15

N/C

22

23

_

24

+

13

14

+

15

_

13

14



23

24



Advertising