West Control Solutions 8700+ User Manual

Page 64

Advertising
background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual


59305, Issue 7

– March 2014

P6100, P8100 & P4100 Model Group

Page 59

Parameter

Modbus

Parameter No.

ASCII Ident &

Message Types

Notes

Secondary
Proportional Band

5

R/W

U

Type 2, 3/4

R/W

Adjustable 0.0% to 999.9% of input
span. Read only when Self-Tuning.

Primary
Proportional Band

6

R/W

P

Type 2, 3/4

R/W

Adjustable 0.0% to 999.9% of input
span. Read only when Self-Tuning.

Direct / Reverse
Acting

7

R/W

1 = Direct Acting, 0 = Reverse

Automatic Reset
Time
(or Loop Alarm
Time)

8

R/W

I

Type 2, 3/4


R/W

Integral Time Constant value.
(or Loop Alarm Time value in ON/OFF
control mode if Loop Alarm Enabled)
Read only if Self-Tuning.
ASCII range: 0 to 99m 59sec (99.59)
Modbus range: 0 to 5999

Rate

9

R/W

D

Type 2, 3/4

R/W

Derivative Time Constant value.
Read only if Self-Tuning.
ASCII range: 0 to 99m 59secs. (99.59)
Modbus range: 0 to 5999

Output 1
Cycle time

10

R/W

N

Type 2

Type 3/4

RO

R/W

0.5, 1, 2, 4, 8, 16, 32, 64,128, 256 or
512 seconds.

Scale Range
Lower Limit

11

R/W

H

Type 2

Type 3/4

RO

R/W

Lower limit of scaled input range

Scale Range
Upper Limit

12

R/W

G

Type 2

Type 3/4

RO

R/W

Upper limit of scaled input range

Alarm 1 Value

13

R/W

C

Type 2, 3/4

R/W

Alarm 1 active at this level

Alarm 2 Value

14

R/W

E

Type 2, 3/4

R/W

Alarm 2 active at this level

Manual Reset

15

R/W

J

Type 2, 3/4

R/W

Bias value. 0% to 100% for single
control output or
-100% to +100% for dual outputs

Overlap /
Deadband

16

R/W

K

Type 2, 3/4

R/W

20% to +20% of



+



;

Negative value = Deadband
Positive value = Overlap

On / Off Differential

17

R/W

F

Type 2, 3/4

R/W

0.1% to 10.0% of input span
Used for Primary output on/off
differential and for combined Primary
and Secondary on/off differential.

Decimal Point
Position

18

R/W

Q

Type 2

Type 3/4

RO

R/W

0 = xxxx
1 = xxx.x
2 = xx.xx
3 = x.xxx
Read only if not Linear Input.

Output 2
Cycle Time.

19

R/W

O

Type 2

Type 3/4

RO

R/W

0.5, 1, 2, 4, 8, 16, 32, 64,128, 256 or
512 seconds.

Advertising