West Control Solutions 8700+ User Manual

Page 86

Advertising
background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual


59305, Issue 7

– March 2014

P6170, P8170 & P4170 Model Group

Page 81

Parameter

Modbus

Parameter No.

Notes

Rate

9

R/W

Derivative Time Constant value.
Read only if Self-Tuning.
Adjustable 0 to 5999

Motor Travel Time

10

R/W

Adjustable 5 to 300 seconds

Scale Range
Lower Limit

11

R/W

Lower limit of scaled input range

Scale Range
Upper Limit

12

R/W

Upper limit of scaled input range

Alarm 1 Value

13

R/W

Alarm 1 active at this level

Alarm 2 Value

14

R/W

Alarm 2 active at this level

Decimal Point
Position

18

R/W

0 = xxxx
1 = xxx.x
2 = xx.xx
3 = x.xxx
Read only if not Linear Input.

Minimum Motor On
Time

19

R/W

Adjustable 0 to (Motor Travel Time/10) in 0.1 sec
increments

Actual Setpoint

21

RO

Current (ramping) value of selected setpoint.

Setpoint Upper
Limit

22

R/W

Maximum setpoint value. Current SP to Input Range
Maximum

Setpoint Lower
Limit

23

R/W

Minimum setpoint value. Current SP to Input Range
Minimum

Setpoint Ramp
Rate

24

R/W

0 = 0ff, 1 to 9999 increments / hour. Dec Point position
as for input range.

Input Filter Time
Constant

25

R/W

0 to 100 seconds

Process Value
Offset

26

R/W

Modified PV = Actual PV + PV Offset. Limited by Scale
Range Maximum and Scale Range Minimum.

Re-transmit Output
Maximum

27

R/W

Maximum scale value for retransmit output, 1999 to
9999. This parameter applies to the first re-transmit
output fitted (see also parameters 2214, 2224 & 2234).

Re-transmit Output
Minimum

28

R/W

Minimum scale value for retransmit output, 1999 to 9999.
This parameter applies to the first re-transmit output fitted
(see also parameters 2215, 2225 & 2235).

Setpoint 2

29

R/W

Value of Setpoint 2

Remote Setpoint

30

RO

Value of Remote Setpoint.
Returns 0FFFFhex if RSP not fitted.

Remote Setpoint
Offset

31

R/W

Modified RSP = Actual RSP + RSP Offset. Limited by
Scale Range Maximum and Scale Range Minimum.

Alarm 1 Hysteresis

32

R/W

0 to 100% of span

Alarm 2 Hysteresis

33

R/W

0 to 100% of span

Setpoint 1

34

R/W

Value of Setpoint 1

Setpoint Select

35

R/W

Shows which is the currently selected active setpoint. If a
digital input has been configured for Setpoint Select, it
will take priority over this parameter
1 = SP1 or LSP, 2 = SP2, 100hex = RSP

Equipment ID

122

RO

The four digit model number 6170