P6100, P8100 & P4100 Model Group

59305, Issue 7

– March 2014

Parameter

Lower
Display

Upper
Display

Description

Default

Value

When
Visible

Decimal point
position





Decimal point position in
non-temperature ranges.
0 = XXXX
1 = XXX.X
2 = XX.XX
3 = X.XXX





=

mV, V or
mA







Control Type





Primary control 



Always



Primary and Secondary
control (e.g. for heat & cool)

Primary Output
Control Action





Reverse Acting



Always



Direct Acting

Alarm 1Type





Process High Alarm



Always



Process Low Alarm



Deviation Alarm



Band Alarm



No alarm

Process High
Alarm 1 value*



Range Min. to Range Max.
Parameter repeated in Setup Mode

Range

Max.

=


Process Low
Alarm 1 value*



Range Min. to Range Max
Parameter repeated in Setup Mode

Range

Min.

=


Deviation
Alarm 1 Value*



span from setpoint

Parameter repeated in Setup Mode



=


Band Alarm 1
value*



1 LSD to full span from setpoint.
Parameter repeated in Setup Mode



=


Alarm 1
Hysteresis*



1 LSD to 100% of span (in display units)
on “safe” side of alarm point.
Parameter repeated in Setup Mode



Always

Alarm 2 Type



As for alarm 1 type



Always

Process High
Alarm 2 value*



Range Min. to Range Max.
Parameter repeated in Setup Mode

Range

Max.

=


Process Low
Alarm 2 value*



Range Min. to Range Max.
Parameter repeated in Setup Mode

Range

Min.

=


Deviation
Alarm 2 Value*



span from setpoint.

Parameter repeated in Setup Mode



=


Band Alarm 2
value*



1 LSD to full span from setpoint.
Parameter repeated in Setup Mode





=



Alarm 2
Hysteresis*



1 LSD to 100% of span (in display units)
on “safe” side of alarm point.
Parameter repeated in Setup Mode



Always

Loop Alarm
Enable



 (disabled) or
 (enabled)



Always