- DIN Controllers & Indicators - Product Manual


Page 86

P6700, P8700& P4700 Model Group

59305, Issue 7

– March 2014

Parameter

Lower
Display

Upper
Display

Description

Default
Value

When
Visible

Decimal point
position





Decimal point position in
non-temperature ranges.
0 = XXXX
1 = XXX.X
2 = XX.XX
3 = X.XXX





=

mV, V or
mA







Process
Variable Offset



Span of controller (see

CAUTION

note

at end of section)



Always

Limit Action





High Limit. Limit relay is
energised when process
“safe” (PV < Limit Setpoint)



Always



Low Limit. Limit relay is
energised when process
“safe” (PV > Limit Setpoint)

Setpoint Upper
Limit



Current Setpoint value to Scale Range
Maximum

Range

Max.

Always

Setpoint Lower
Limit



Scale Range Minimum to current Setpoint
value

Range

Min

Always

Alarm 1Type





Process High Alarm



Always



Process Low Alarm



Deviation Alarm



Band Alarm



No alarm

Process High
Alarm 1 value*



Range Min. to Range Max.

Range

Max.

=


Process Low
Alarm 1 value*



Range Min. to Range Max

Range

Min.

=


Deviation
Alarm 1 Value*



span from setpoint



=


Band Alarm 1
value*



1 LSD to full span from setpoint.



=


Alarm 1
Hysteresis*



1 LSD to 100% of span (in display units)
on “safe” side of alarm point.



Always

Alarm 2 Type



As for alarm 1 type



Always

Process High
Alarm 2 value*



Range Min. to Range Max.

Range

Max.

=


Process Low
Alarm 2 value*



Range Min. to Range Max.

Range

Min.

=


Deviation
Alarm 2 Value*



span from setpoint.



=


Band Alarm 2
value*



1 LSD to full span from setpoint.





=

