Option slot 3 - relay output module, Option slot 3 - ssr driver output module, Po2-c50 – West Control Solutions 8700+ User Manual

Page 36: Ssr driver, Po2-c21, Linear ma/v dc, Po2-w09, Dual relay

Advertising
background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual


59305, Issue 7

– March 2014

Connections

Page 31

Option Slot 3 - Relay Output Module

If option slot 3 is fitted with a relay output module, make connections as illustrated. The relay
contacts are rated at 2 amps resistive, 240 VAC (120V max for direct Valve Motor control).

1

/

16

DIN

1

/

4

DIN &

1

/

8

DIN

Figure 27.

Option Slot 3 - Relay Module

Option Slot 3 - SSR Driver Output Module

If option slot 3 is fitted with an SSR driver output module, make connections as illustrated.
The solid-state relay driver is a 0-10V DC signal; load resistance must be no less than 500
ohms. SSR driver outputs are not isolated from the signal input or other SSR driver outputs.

1

/

16

DIN

1

/

4

DIN &

1

/

8

DIN

Figure 28.

Option Slot 3 - SSR Driver Module

Option Slot 3 - Linear Voltage or mADC Output module

If option slot 3 is fitted with a DC linear output module, make connections as illustrated.

1

/

16

DIN

1

/

4

DIN &

1

/

8

DIN

Figure 29.

Option Slot 3 - Linear Voltage & mADC module

10

11

_

12

+

16

17

_

18

+

10

11

_

12

+

16

17

_

18

+

10

11

N/C

COM

12

N/O

16

17

N/C

COM

18

N/O

Advertising