Warning, Caution – Allied Air Enterprises A95DF User Manual

Page 10

Advertising
background image

506725-01

Page 10 of 48

Issue 1109

WARNING

Improper installation of the furnace can result in personal

injury or death. Combustion and flue products must

never be allowed to enter the return air system or air in

the living space. Use sheet metal screws and joint tape

to seal return air system to furnace.

In platform installations with furnace return, the furnace

should be sealed airtight to the return air plenum. A

door must never be used as a portion of the return air

duct system. The base must provide a stable support

and an airtight seal to the furnace. Allow absolutely no

sagging, cracks, gaps, etc.

For no reason should return and supply air duct systems

ever be connected to or from other heating devices such

as a fireplace or stove, etc. Fire, explosion, carbon

monoxide poisoning, personal injury and/or property

damage could result.

Installation on Non-Combustible Flooring (Figure 12)

1. Cut floor opening keeping in mind clearances listed on

unit rating plate. Also keep in mind gas supply

connections, electrical supply, flue and air intake

connections and sufficient installation and servicing

clearances. See Table 1 for correct floor opening size.

2. Flange warm air plenum and lower the plenum into the

opening.

3. Set the unit over the plenum and seal the plenum to the

unit.

4. Ensure that the seal is adequate.

Installation on Combustible Flooring (Figure 13)

1. When unit is installed on a combustible floor, a downflow

combustible flooring base must be installed between the

furnace and the floor. The base must be ordered

separately. See Table 2 for opening size to cut in floor.

CAUTION

The furnace and combustible flooring base shall not be

installed directly on carpeting, tile, or other combustible

material other than wood flooring.

The unit may be installed three ways in downflow applica-

tions: on non-combustible flooring, on combustible flooring

using an additive base, or on a reverse-flow cooling coil

cabinet. Do not drag the unit across the floor in the

downflow position. Floor and furnace flange damage

will result.

Refer to Figure 11 for clearances in downflow applica-

tions.

Downflow Application Installation Clearances

Top

Bottom

Left Side

Right Side

Top

0

*Front

0

Back

0

Sides

0†

Vent

0

Floor

NC ‡

*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
†Allow proper clearances to accommodate condensate trap.
‡The furnace may be installed on a combustible wood floor if an optional
additive base is installed between the furnace and the combustible floor.

FIGURE 11

FIGURE 12

SUPPLY AIR

PLENUM

PROPERLY

SIZED FLOOR

OPENING

FURNACE

TABLE 1

NON−COMBUSTIBLE FLOOR OPENING SIZE

Cabinet Width

Front to Rear

Side to Side

in .

mm

in.

mm

B Cabinet (17.5")

19 − 3/4

502

16 − 5/8

422

C Cabinet (21")

19 − 3/4

502

20−1/8

511

NOTE: Floor opening dimensions listed are 1/4 inch (6 mm) larger than
the unit opening. See dimension drawing on page 2.