Allied Air Enterprises A95DF User Manual

Page 22

Advertising
background image

506725-01

Page 22 of 48

Issue 1109

FIGURE 27

C

A

E

D

B

A

B

D

D

B

C

A

C

12"

1

1

2

2

2" (51mm)

Vent Pipe

3" (76mm)

Vent Pipe

A − Clearance above

grade or average snow

accumulation

B −Horizontal

separation between

intake and exhaust

C −Minimum from

end of exhaust to

inlet of intake

D−Exhaust pipe length

E −Wall support distance

from top of each pipe

(intake/exhaust)

12" (508MM) Min.

12" (508MM) Min.

6" (152MM) Min.

24" (610 MM) Max

9" (227MM) Min.

12" (305MM) Min.
16" (405 MM) Max.

6" (152MM) Max.

6" (152MM) Min.

24" (610 MM) Max

9" (227MM) Min.

12" (305MM) Min.
20" (508MM) Max.

6" (152MM) Max.

TABLE 9

1

The exhaust termination tee should be connected to the 2" or 3" PVC flue pipe as shown in the illustration. Do

not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.

2

As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent

termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield (24 inches
square) should be used to protect the wall surface. If optional tee is used, the protective shield is recom-
mended. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints,
cracks, etc. in affected area, should be sealed using an appropriate sealant.

3

Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away

from adjacent property. The exhaust must never be directed toward the combustion air inlet.

Front View of

Intake and Exhaust

Intake

Exhaust

3

Intake

Exhaust