Allied Air Enterprises A95DF User Manual

Page 16

Advertising
background image

506725-01

Page 16 of 48

Issue 1109

TABLE 7

Maximum Allowable Intake or Exhaust Vent Length in Feet

*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total.

Both Intake and Exhaust must be same pipe size.

Standard Termination at Elevation 0 − 10,000 ft.

Number

Of 90°

Elbows

Used

2" Pipe

2−1/2" Pipe

3" Pipe

Model

Model

Model

045

070

090

110

045

070

090

110

045

070

090

110

1

61

46

24

n/a

100

80

43

n/a

127

127

108

108

2

56

41

19

95

75

38

122

122

103

103

3

51

36

14

90

70

33

117

117

98

98

4

46

31

n/a

85

65

28

112

112

93

93

5

41

26

80

60

23

107

107

88

88

6

36

21

75

55

18

102

102

83

83

7

31

16

70

50

13

97

97

78

78

8

26

11

65

45

n/a

92

92

73

73

9

21

n/a

60

40

87

87

68

68

10

16

55

35

82

82

63

63

Concentric Termination Elevation 0 − 10,000 ft.

Number

Of 90°

Elbows

Used

2" Pipe

2−1/2" Pipe

3" Pipe

Model

Model

Model

045

070

090

110

045

070

090

110

045

070

090

110

1

53

38

22

n/a

90

70

39

n/a

111

111

104

104

2

48

33

17

85

65

34

106

106

99

99

3

43

28

12

80

60

29

101

101

94

94

4

38

23

n/a

75

55

24

96

96

89

89

5

33

18

70

50

19

91

91

84

84

6

28

13

65

45

14

86

86

79

79

7

23

n/a

60

40

n/a

81

81

74

74

8

18

55

35

76

76

69

69

9

13

50

30

71

71

64

64

10

n/a

45

25

66

66

59

59

A95DF / 95G1DF and A93DF / 92G1DF