Figure 30, Figure 31, Figure 32 – Allied Air Enterprises A95DF User Manual

Page 24: Front view, Side view, Direct vent application using existing chimney, Figure 33

Advertising
background image

506725-01

Page 24 of 48

Issue 1109

FIGURE 30

DIRECT VENT CONCENTRIC ROOFTOP TERMINATION

71M80, 69M29 or 60L46 (US)

44W92 or 44W93 (Canada)

Minimum

Above Average

Snow

Accumulation

SHEET METAL STRAP

(Clamp and sheet metal strap

must be field installed to support
the weight of the termination kit.)

FLASHING

(Not Furnished)

CLAMP

FIELD−PROVIDED

REDUCER MAY BE REQUIRED

TO ADAPT LARGER VENT

PIPE SIZE TO TERMINATION

1 1/2" (38mm) accelerator

provided on 71M80 & 44W92

12” (305mm)

INTAKE

AIR

EXHAUST

VENT

12" (305mm) Min.

above grade or

average snow
accumulation.

FIGURE 31

DIRECT VENT CONCENTRIC WALL TERMINATION

71M80, 69M29 or 60L46 (US)

44W92 or 44W93 (Canada)

INTAKE

AIR

INTAKE

AIR

INTAKE

AIR

OUTSIDE

WALL

GRADE

CLAMP

(Not Furnished)

FIELD−PROVIDED

REDUCER MAY BE REQUIRED

TO ADAPT LARGER VENT

PIPE SIZE TO TERMINATION

EXHAUST

VENT

1−1/2" (38mm) accelerator

provided on 71M80 & 44W92

EXHAUST

VENT

FIGURE 32

EXHAUST

VENT

INTAKE

AIR

5−1/2"

(140mm)

Front View

12"

(305mm)

5"

(127mm)

18" MAX.

(457mm)

EXHAUST VENT

INTAKE

AIR

OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT

INSTALLATION OF DIRECT VENT WALL TERMINATION KIT

Inches (mm)

Side View

12" (305mm) Min.

above grade or

average snow

accumulation.

optional intake elbow

DIRECT VENT APPLICATION

USING EXISTING CHIMNEY

NOTE − Do not discharge exhaust gases directly into any chimney or vent st ack. If ver-
tical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illus-
trated. In any exterior portion of chimney, the exhaust vent must be insulated.

FIGURE 33

3" − 8"

(76mm−

203mm)

STRAIGHT−CUT OR

ANGLE−CUT IN DIRECTION

OF ROOF SLOPE *

EXHAUST VENT

1/2" (13mm)

WEATHERPROOF

INSULATION

SHOULDER OF FITTINGS

PROVIDE SUPPORT

OF PIPE ON TOP PLATE

ALTERNATE

INTAKE PIPE

INTAKE PIPE

INSULATION (optional)

EXTERIOR

PORTION OF

CHIMNEY

INSULATE

TO FORM

SEAL

SHEET

METAL TOP

PLATE

*SIZE TERMINATION

PIPE PER TABLE 6.

Minimum 12" (305MM)

above chimney top

plate or average snow

accumulation

8" − 12"

(203mm − 305mm)

3"−8"

(76mm−203mm)

Advertising
This manual is related to the following products: