BLOWER DATA A95DF1D / 95G1DF

A95DF1D / 95G1DF 070*12B PERFORMANCE (Less Filter)

External

Static

Pressure

in. w.g.

Air Volume / Watts at Various Blower Speeds

High

Medium-

High

Medium-

Low

Low

cfm Watts cfm Watts cfm Watts cfm Watts

0.00

1515

620

1315

545

1095

465

910

390

0.10

1490

585

1300

525

1075

445

890

375

0.20

1445

555

1275

500

1065

425

910

360

0.30

1380

520

1240

470

1060

400

900

340

0.40

1315

495

1190

440

1020

385

875

325

0.50

1270

470

1145

420

995

355

870

310

0.60

1155

435

1075

390

940

330

820

300

0.70

1075

415

1000

355

875

310

765

270

0.80

975

380

900

325

800

285

715

250

0.90

900

365

800

300

675

255

615

225

A95DF1D /95G1DF 110*20C PERFORMANCE (Less Filter)

External

Static

Pressure

in. w.g.

Air Volume / Watts at Various Blower Speeds

High

Medium-

High

Medium-

Low

Low

cfm Watts cfm Watts cfm Watts cfm Watts

0.00

2375 1250 2205

915

1975

785

1630

640

0.10

2365 1235 2195

905

1960

775

1625

635

0.20

2275 1200 2125

890

1950

760

1635

625

0.30

2200 1180 2060

880

1900

735

1620

610

0.40

2115 1150 1995

850

1845

710

1620

600

0.50

2040 1115 1940

835

1795

695

1585

580

0.60

1955 1090 1855

810

1745

670

1540

565

0.70

1860 1070 1730

765

1640

650

1515

550

0.80

1735 1030 1620

740

1590

620

1415

535

0.90

1640 1010 1535

715

1480

600

1330

510

A95DF1D / 95G1DF 045*12B PERFORMANCE (Less Filter)

External

Static

Pressure

in. w.g.

Air Volume / Watts at Various Blower Speeds

High

Medium-

High

Medium-

Low

Low

cfm Watts cfm Watts cfm Watts cfm Watts

0.00

1615

650

1385

555

1205

465

1045

390

0.10

1605

640

1380

545

1195

455

1035

380

0.20

1500

620

1345

525

1165

445

1015

370

0.30

1450

590

1290

490

1125

420

975

365

0.40

1350

560

1235

480

1090

405

920

345

0.50

1300

545

1170

450

1035

380

880

330

0.60

1195

500

1095

425

990

365

840

320

0.70

1140

480

1020

395

895

345

780

300

0.80

1025

450

920

370

840

330

695

270

0.90

945

430

800

335

700

290

605

250

A95DF1D / 95G1DF 090*20C PERFORMANCE (Less Filter)

External

Static

Pressure

in. w.g.

Air Volume / Watts at Various Blower Speeds

High

Medium-

High

Medium-

Low

Low

cfm Watts cfm Watts cfm Watts cfm Watts

0.00

2305 1255 2145

950

1900

810

1515

670

0.10

2295 1240 2135

940

1885

795

1500

665

0.20

2200 1220 2085

915

1865

775

1525

655

0.30

2160 1210 1990

875

1830

755

1545

640

0.40

2055 1170 1935

865

1790

725

1530

620

0.50

1970 1130 1855

835

1705

700

1500

600

0.60

1890 1105 1765

805

1635

675

1495

580

0.70

1775 1075 1680

785

1565

655

1430

560

0.80

1690 1050 1590

760

1485

630

1370

540

0.90

1580 1010 1485

735

1405

610

1270

510

NOTES: All air data is measured external to unit without filter (not furnished - field provided)