Allied Air Enterprises A95DF User Manual

Page 32

Advertising
background image

506725-01

Page 32 of 48

Issue 1109

One line voltage “HUM” 1/4” spade terminal is provided on

the furnace control board. Any humidifier rated up to one

amp can be connected to this terminal with the neutral leg

of the circuit being connected to one of the provided neutral

terminals. If a humidifier rated at greater than one amp is

connected to this terminal, it is necessary to use an external

relay. See Figure 49 for control board configuration. This

terminal is energized in the heating mode when the

combustion air inducer is operating.

Install the room thermostat according to the instructions

provided with the thermostat. See Figure 46 for thermostat

designations. If the furnace is being matched with a heat

pump, refer to the FM21 installation instruction or appropriate

dual fuel thermostat instructions.

Generator Use - Voltage Requirements

The following requirements must be kept in mind when

specifying a generator for use with this equipment:

The furnace requires 120 volts ± 10% (Range: 108 volts

to 132 volts).

The furnace operates at 60 Hz ± 5% (Range: 57 Hz to

63 Hz).

The furnace integrated control requires both polarity and

proper ground. Both polarity and proper grounding

should be checked before attempting to operate the

furnace on either permanent or temporary power.

Generator should have a wave form distortion of less

than 5% THD (total harmonic distortion).

Indoor Blower Speeds

1. When the thermostat is set to “FAN ON”, the indoor

blower will run continuously on the heating speed when

there is no cooling or heating demand.

2. When the furnace is running in the heating mode, the

indoor blower will run on the heating speed.

3. When there is a cooling demand, the indoor blower will

run on the cooling speed.

Thermostat

Furnace

Condensing

Unit

FURNACE and CONDENSING UNIT

THERMOSTAT DESIGNATIONS

(Refer to specific thermostat and outdoor unit.)

COMMON

POWER

HEAT

INDOOR BLOWER

Y

C

R

G

W1

Y

C

R

G

W

COOLING

FIGURE 46

CONDENSING

CONDENSING

*CONDENSING

TYPICAL FIELD WIRING DIAGRAM

FIGURE 47

IGNITOR

*R

Advertising
This manual is related to the following products: