Details of Intake and Exhaust Piping Terminations for

Direct Vent Installations

NOTE: In Direct Vent installations, combustion air is taken

from outdoors and flue gases are discharged to outdoors.

NOTE: Flue gas may be slightly acidic and may adversely

affect some building materials. If any vent termination is

used and the flue gases may impinge on the building

material, a corrosion-resistant shield (minimum 24 inches

square) must be used to protect the wall surface. If the

optional tee is used, the protective shield is required. The

shield should be constructed using wood, plastic, sheet metal

or other suitable material. All seams, joints, cracks, etc. in

the affected area should be sealed using an appropriate

sealant. See Figure 27.

Intake and exhaust pipes may be routed either horizontally

through an outside wall or vertically through the roof. In

attic or closet installations, vertical termination through the

roof is preferred. Figures 25 through 33 show typical

terminations.

1. Exhaust and intake exits must be in same pressure zone.

Do not exit one through the roof and one on the side.

Also, do not exit the intake on one side and the exhaust

on another side of the house or structure.

2. Intake and exhaust pipes should be placed as close

together as possible at termination end (refer to

illustrations). Maximum separation is 3" (76 mm) on

roof terminations and 6" (152 mm) on side wall

terminations.

3. On roof terminations, the intake piping should terminate

straight down using two 90° elbows (See Figure 25).

4. Exhaust piping must terminate straight out or up as

shown. A reducer may be required on the exhaust piping

at the point where it exits the structure to improve the

velocity of exhaust away from the intake piping. See

Table 8.

6. On field supplied terminations, a minimum distance

between the end of the exhaust pipe and the end of the

intake pipe without a termination elbow is 8" and a

minimum distance of 6" with a termination elbow. See

Figures 28 and 29.

7. If intake and exhaust piping must be run up a side wall

to position above snow accumulation or other

obstructions, piping must be supported every 24" (610

mm) as shown in Figures 28 and 29.

When exhaust and intake piping must be run up an

outside wall, the exhaust piping must be terminated with

pipe sized per Table 8. The intake piping may be

equipped with a 90° elbow turndown. Using turndown

will add 5 feet (1.5 m) to the equivalent length of the

pipe.

8. Based on the recommendation of the manufacturer, a

multiple furnace installation may use a group of up to

four terminations assembled together horizontally, as

shown in Figure 32.

TABLE 8

EXHAUST PIPE TERMINATION SIZE REDUCTION

MODEL

Exhaust Pipe Size

Termination

Pipe Size

*045 and *070

2" (51mm), 2−1/2" (64mm),

3" (76mm)

1−1/2" (38mm)

*090

2" (51mm)

110

3" (76mm)

2" (51mm)

*045, 070 and 090 units with the flush−mount termination
must use the 1−1/2"accelerator supplied with the kit.

5. On field supplied terminations for side wall exit, exhaust

piping may extend a maximum of 12 inches (305 mm)

for 2" PVC and 20 inches (508 mm) for 3" (76 mm) PVC
beyond the outside wall. Intake piping should be as
short as possible. See Figures 28 and 29.

NOTE: Care must be taken to avoid recirculation of exhaust

back into intake pipe.

2" EXTENSION
FOR 2" PVC PIPE
1" EXTENSION
FOR 3" PVC PIPE

FIGURE 26

1−1/2" ACCELERATOR

(

all −45, −070 and −090 units)

FURNACE

EXHAUST

PIPE

FURNACE

INTAKE PIPE

4’’

GLUE EXHAUST

END FLUSH INTO

TERMINATION

FLAT SIDE

FLUSH−MOUNT SIDE WALL TERMINATION

51W11

FIGURE 25

UNCONDITIONED

ATTIC SPACE

1/2" (13mm) FOAM

INSULATION IN

UNCONDITIONED

SPACE

SIZE TERMINATION

PIPE PER TABLE 8.

3"(76mm) MAX.

12" (305mm) ABOVE

AVERAGE SNOW

ACCUMULATION

3" (76mm) OR

2" (51mm) PVC

PROVIDE SUPPORT

FOR INTAKE AND

EXHAUST LINES

8" (203mm) MIN

Inches(mm)

DIRECT VENT ROOF TERMINATION KIT

(15F75 or 44J41)

(IF REQUIRED)