2.

After opening is cut, set the combustible flooring base
into opening.

3. Check fiberglass strips on the combustible flooring base

to make sure they are properly glued and positioned.

4.

Lower supply air plenum into the combustible flooring
base until plenum flanges seal against fiberglass strips.

er opening is

NOTE: Be careful not to damage fiberglass strips. Check
for
a tight seal.

5.

Set the furnace over the plenum.

6. Ensure that the seal between the furnace and plenum

is adequate.

Installation on Cooling Coil Cabinet (Figure 14)

NOTE: Downflow combustible flooring kit is not used.

1.

Refer to reverse-flow coil installation instructions for
correctly sized opening in floor and installation of
cabinet.

2. When cooling cabinet is in place, set and secure the

furnace according to the instructions that are provided
with the cooling coil. Secure the furnace to the cabinet.

3.

Seal the cabinet and check for air leaks.

Return Air Opening - Downflow Units

Return air may be brought in only through the top opening

of a furnace installed in the downflow position. The following

steps should be taken when installing plenum:

1. Bottom edge of plenum should be flanged with a

hemmed edge (See Figure 15 or 16).

2. Sealing strips should be used to ensure an airtight seal

between the cabinet and the plenum.

3. In all cases, plenum should be secured to top of furnace

using sheet metal screws.

4. Make certain that an adequate seal is made.

TABLE 2

COMBUSTIBLE FLOORING BASE OPENING SIZE

Cabinet

Width

Catalog

Number

Front to Rear

Side to Side

in.

mm

in.

mm

B Cabinet

(17.5")

11M60

22

559

18 − 3/4

476

C Cabinet

(21")

11M61

22

559

22 − 3/4

578

FIGURE 13

FURNACE

SUPPLY AIR

PLENUM

COMBUSTIBLE
FLOORING BASE

PROPERLY

SIZED FLOOR

OPENING

FIGURE 14

COOLING COIL

PLENUM

PROPERLY

SIZED FLOOR

OPENING

FURNACE

FIGURE 15

SECURE FROM

OUTSIDE CABINET

PLENUM

(Field Provided)

SEALING STRIP

(Field Provided)

Side View

CABINET

SIDE PANEL

SECURE FROM

INSIDE CABINET

PLENUM

(Field Provided)

SEALING STRIP

(Field Provided)

Side View

CABINET

SIDE PANEL

FIGURE 16