Allied Air Enterprises A95DF User Manual

Page 5

Advertising
background image

506725-01

Page 5 of 48

Issue 1109

Locations and Clearances

This furnace is CSA International certified for installation

clearances to combustible material as listed on the unit

nameplate and in the table in Figure 11. Accessibility and

service clearances must take precedence over fire protection

clearances.

NOTE: When furnace is installed on a combustible floor, a

downflow combustible flooring base must be installed

between the furnace and the floor.

For installation in a residential garage, the furnace must be

installed so that the burner(s) and the ignition source are

located no less than 18 inches (457 mm) above the floor.

The furnace must be located or protected to avoid physical

damage by vehicles. When a furnace is installed in a public

garage, hangar, or other building that has a hazardous

atmosphere, the furnace must be installed according to

recommended good practice requirements and current

National Fuel Gas Code or CSA B149 standards.

Note: Furnace must be adjusted to obtain a temperature

rise within the range specified on the unit nameplate. Failure

to do so may cause erratic limit operation and premature

heat exchanger failure.

This gas furnace must be installed so that its electrical

components are protected from water.

Installed in Combination with a Cooling Coil

When this furnace is used with cooling units (Figure 3), it

shall be installed in parallel with, or on the upstream side of,

cooling units to avoid condensation in the heating

compartment. With a parallel flow arrangement, a damper

(or other means to control the flow of air) must adequately

prevent chilled air from entering the furnace. If the damper

is manually operated, it must be equipped to prevent

operation of either the heating or the cooling unit, unless it

is in the full HEAT or COOL setting.

When installed, this furnace must be electrically grounded

according to local codes. In addition, in the United States,

installation must conform with the current National Electric

Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/

NFPA No. 70) is available from the following address:

National Fire Protection Association

1 Battery March Park

Quincy, MA 02269

In Canada, all electrical wiring and grounding for the unit

must be installed according to the current regulations of the

Canadian Electrical Code Part I (CSA Standard C22.1) and/

or local codes.

NOTE: This furnace is designed for a minimum continuous

return air temperature of 60°F (16°C) or an intermittent

operation down to 55°F (13°C) dry bulb for cases where a

night setback thermostat is used. Return air temperature

must not exceed 85°F (29°C) dry bulb.

This gas furnace may be installed in alcoves, closets, attics,

basements, garages, and utility rooms.

This furnace design has NOT been CSA certified for

installation in mobile homes, recreational vehicles, or

outdoors.

Never use an open flame to test for gas leaks. Check all

connections using a commercially available soap solution

made specifically for leak detection.

Use of Furnace as Construction Heater

These units are not recommended for use as a construction

heater during any phase of construction. Very low return air

temperature, harmful vapors and operation of the unit with

clogged or misplaced filters will damage the unit.

These units may be used for heating of buildings or structures

under construction, if the following conditions are met:

The vent system must be permanently installed per these

installation instructions.

A room thermostat must control the furnace. The use of

fixed jumpers that will provide continuous heating is not

allowed.

The return air duct must be provided and sealed to the

furnace.

Return air temperature range between 60°F (16°C) and

80°F (27°C) must be maintained.

Air filters must be installed in the system and must be

maintained during construction.

FIGURE 3

Heating Unit Installed Parallell to Air Handler Unit

AIR HANDLER

GAS UNIT

Dampers

(open during cooling

operation only)

Dampers

(open during heating

operation only)

Advertising
This manual is related to the following products: