Allied Air Enterprises A95DF User Manual

Page 36

Advertising
background image

506725-01

Page 36 of 48

Issue 1109

Gas Pressure Adjustment

Gas Flow (Approximate)

NOTE: T

o obtain accurate reading, shut off all other gas

appliances connected to meter.

Furnace should operate at least 5 minutes before checking
gas flow. Determine time in seconds for two revolutions of
gas through the meter. (Two revolutions assures a more
accurate time.) Divide by two and compare to time in
Table 11. If manifold pressure matches Table 12 and rate
is incorrect, check gas orifices for proper size and restriction.
Remove temporary gas meter if installed.

Supply Pressure Measurement
A threaded plug on the inlet side of the gas valve provides

access to the supply pressure tap. Remove the threaded

plug, install a field-provided barbed fitting and connect a

manometer to measure supply pressure. Replace the

threaded plug after measurements have been taken.

Manifold Pressure Measurement

1. Remove the threaded plug from the outlet side of the

gas valve and install a field provided barbed fitting.

Connect to a manometer to measure manifold pressure.

2. Start unit and allow 5 minutes for unit to reach steady

state.

3. While waiting for the unit to stabilize, observe the flame.

Flame should be stable and should not lift from burner.

Natural gas should burn blue.

4. After allowing unit to stabilize for 5 minutes, record

manifold pressure and compare to value given in

Table 12.

NOTE: Shut unit off and remove manometer as soon as

an accurate reading has been obtained. Take care to remove
barbed fitting and replace threaded plug.

Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking
combustion. Take combustion sample beyond the flue outlet
and compare to the tables below. The maximum carbon
monoxide reading should not exceed 50 ppm.

High Altitude Information

NOTE: In Canada, certification for installations at elevations

over 4500 feet (1372 m) is the jurisdiction of local authorities.

The furnace requires no manifold pressure adjustments for
operation at altitudes up to 10,000 feet (3048 m) above sea
level. Units installed at altitudes of 4501 - 10,000 feet (1373
to 3048 m) require a pressure switch change which can be
ordered separately. Table 14 lists conversion kit and
pressure switch requirements at varying altitudes.

The combustion air pressure switch is factory-set and
requires no adjustment.

TABLE 11

GAS METER CLOCKING CHART

Unit

Seconds for One Revolution

Natural

LP

1 cu ft

Dial

2 cu ft

Dial

1 cu ft

Dial

2 cu ft

DIAL

−045

80

160

200

400

−070

55

110

136

272

−090

41

82

102

204

−110

33

66

82

164

−135

27

54

68

136

Natural−1000 btu/cu ft LP−2500 btu/cu ft

TABLE 12

Supply Line and Manifold Pressure (inches w.c.)

Unit

Fuel

Manifold

Pressure

Line Pressure

All

Nat. Gas

3.5

4.5 − 10.5

All

L.P. Gas

10.0

11.0 − 13.0

NOTE:

A natural to L.P. propane gas changeover kit is necessary

to convert this unit. Refer to the changeover kit installation

instruction for the conversion procedure.

TABLE 13

Unit

CO

2

%

For Nat

CO

2

%

For L.P.

7.2 − 7.9

8.6 − 9.3

The maximum carbon monoxide reading should not exceed 50 ppm.

All

Advertising
This manual is related to the following products: