Chapter Five--Control Setup

Selecting breakers for Emergency
Shutdown, Emergency Lighting or
Brownout

Figure 5-17

Select breakers to actuate in
the event of a brownout in
green outlined check boxes.

Select breakers for
emergency shutdown in
pink outlined check boxes.

Select breakers to actuate in the event of a brownout by
checking the green box next to the breaker. Select breakers to
turn on in the event of a fi re or other emergency by checking
the yellow box next to the breaker. Select breakers to turn off
in the event of a fi re or other emergency by checking the red
box next to the breaker. The status of unchecked breakers will
remain unaff ected.

Brownout Thresholds (optional)

If the brownout feature has been selected, the nominal AC
Voltage should be set for proper operation. Click the pull
down menu in the brownout VAC box and select the nominal
operation voltage for the panel (100-240 VAC) The brownout
thresholds will automatically adjust for shutoff at nominal -20%
and recovery at nominal -10%..

Figure 5-18

Before:

After:

Select breakers for emergency
lighting in yellow outlined
check boxes.