Appendix A

Events include:

Event 1 = “All Breakers ON”

Event 2 = “All Breakers OFF”

Event 3 = “Hurry OFF” zips all breakers off fast.

Event 4 = “EO” Emergency override (status only)

Event 5 = “Audio Timer” (NA) (status only)

Event 6 = “BO” Brown-Out (status only

Event 7 = “DMX/sACN”

Event 8 = “EL” Emergency Lighting

Verifi cation Scheme:

The following GET command will return the current status of all
breakers, zones and events in the RPC system.

GET /p2.rpc

The system will return the following:

breakers=10110111111111111111

zones=111111111011

events=1000000

The above return is displaying the status of a 20 circuit breakers
system in which all are presently ON, with the exceptions of
breaker #2 and breaker #5, which are OFF.

The above return is also showing the status of 12 zones, all are
ON with the exception of zone #10, which is OFF.

The events return is showing that event #1 is active = “All
Breakers ON”

Status returns for
Breakers:

Status returns for Zones
and Events:

0 = OFF

0 = OFF

1 = ON

1 = ON

2 = Breaker Tripped

2 = Processing

3 = Failure
4 = Manual On
5 = Empty

Events Control = E