Appendix A--TCP/IP Protocol

TCP/IP PROTOCOL

TCP/IP communications and control via a third party control
system is facilitated by the use of the HTTP GET command.

Example of GET command:
GET /p2.rpc?IPB002=1

Three modes of control are:

Breaker control = “B” Zone control = “Z” Event Control = “E”

Refer to LynTec RPC browser set-up for breaker numbering

GET /p2.rpc?IPB002=1
This control string will turn breaker #2 on.

GET /p2.rpc?IPB002=0
This control string will turn breaker #2 off .

Control of up to 167 breakers (4 panel system) is possible.

Confi gure your zones (breaker groups) using the LynTec RPC
browser set-up when connected to the LynTec RPC panel.

GET /p2.rpc?IPZ002=1
This control string will turn zone #2 on.
GET /p2.rpc?IPZ002=0
This control string will turn zone #2 off .
GET /p2.rpc?IPE001=1
This control string will turn event #1 on.

GET /p2.rpc?IPE001=0
This control string will turn event #1 off .

Zone Control = Z

Breaker Control = B