Bryant 580D User Manual

Page 17

Advertising
background image

BASE UNIT DIMENSIONS — 580D036-072

UNIT
580D

CORNER WEIGHT*

A

B

C

D

lb

kg

lb

kg

lb

kg

lb

kg

036

140

63.5

105

47.6

159

72.1

56

25.4

048

142

64.4

106

48.1

162

73.5

60

27.2

060

150

68.0

115

52.2

160

72.6

65

29.5

072

165

74.8

136

61.7

200

90.7

64

29.0

*

Weights are for unit only (aluminum plate fins) and do not include options or crating.

CONNECTION SIZES

A

1

1

16

Љ

Dia. [27] Field Power

Supply Hole

B

3

4

Љ

— 14 NPT Condensate

Drain

C

1

2

Љ

—14 NPT Gas Connection

BOTTOM POWER CHART, THESE

HOLES REQUIRED FOR USE WITH

ACCESSORY PACKAGES —

CRBTMPWR001A00 (

1

2

Љ

,

3

4

Љ

)

CRBTMPWR002A00 (

1

2

Љ

, 1

1

4

Љ

)

THREADED

CONDUIT

SIZE

WIRE SIZE

REQUIRED

HOLE SIZES

(MAX)

1

2

؆

24 V

7

8

Љ

[22.2]

3

4

؆

Power†

1

1

8

Љ

[28.4]

1

1

4

؆

Power†

1

3

4

Љ

[44.4]

†Select either

3

4

Љ

or 1

1

4

Љ

for power, depending

on wire size.

NOTES:
1. Dimensions in [

] are in millimeters.

2.

Center of gravity.

3.

Direction of airflow.

4. On vertical discharge units, ductwork to be attached to accessory roof curb only.

For horizontal discharge units, field-supplied flanges should be attached to horizon-
tal discharge openings, and all ductwork should be attached to the flanges.

5. Minimum clearance (local codes or jurisdiction may prevail):

a. Between unit, flue side and combustible surfaces, 36 inches.
b. Bottom of unit to combustible surfaces (when not using curb), 1 inch. Bottom of

base rail to combustible surfaces (when not using curb) 0 inches.

c. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side get-

ting the greater clearance is optional.

d. Overhead, 60 in. to assure proper condenser fan operation.
e. Between units, control box side, 42 in. per NEC (National Electrical Code).
f. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
g. Between unit and block or concrete walls and other grounded surfaces, control

box side, 42 in. per NEC.

h. Horizontal supply and return end, 0 inches.

6. With the exception of the clearance for the condenser coil and combustion side as

stated in Notes 5a, b, and c, a removable fence or barricade requires no clearance.

7. Units may be installed on combustible floors made from wood or Class A, B, or C

roof covering material if set on baserail.

8. The vertical center of gravity is 1

Ј

-6

Љ

[457] up from the bottom of the base rail. Hori-

zontal center of gravity is shown.

17