Bryant 580D User Manual

Page 45

Advertising
background image

PERFORMANCE DATA (cont)

FAN PERFORMANCE — 580D036-150 HORIZONTAL DISCHARGE UNITS (cont)

580D120 (10 TONS)*

Airflow

(Cfm)

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3000

552

0.68

661

632

0.87

810

701

1.05

956

761

1.22

1097

816

1.36

1216

871

1.54

1370

3100

565

0.74

708

644

0.93

859

711

1.12

1014

772

1.31

1173

825

1.45

1292

879

1.63

1447

3200

578

0.81

763

656

1.00

916

723

1.20

1081

782

1.39

1241

835

1.55

1378

887

1.71

1517

3300

591

0.88

818

668

1.08

973

734

1.28

1148

793

1.47

1310

845

1.65

1465

895

1.80

1595

3400

605

0.96

883

680

1.16

1047

745

1.36

1216

803

1.56

1387

856

1.75

1552

904

1.91

1691

3500

619

1.04

948

691

1.23

1106

755

1.44

1284

813

1.65

1465

867

1.86

1648

914

2.03

1796

3600

633

1.13

1022

703

1.31

1173

766

1.52

1353

824

1.74

1543

877

1.97

1744

924

2.15

1901

3700

648

1.23

1106

714

1.39

1241

777

1.61

1430

835

1.85

1639

887

2.07

1831

935

2.28

2015

3800

662

1.33

1190

726

1.51

1310

789

1.72

1526

846

1.95

1726

897

2.18

1927

946

2.40

2169

3900

677

1.44

1284

738

1.61

1387

801

1.82

1613

857

2.06

1823

908

2.29

2023

956

2.53

2282

4000

692

1.55

1378

750

1.73

1473

813

1.94

1718

868

2.17

1919

918

2.40

2119

967

2.66

2397

4100

707

1.67

1482

762

1.84

1560

825

2.05

1814

878

2.28

2015

929

2.53

2282

977

2.78

2505

4200

722

1.80

1595

775

1.97

1656

837

2.16

1910

889

2.40

2119

941

2.66

2397

987

2.91

2624

4300

737

1.94

1718

787

2.09

1761

848

2.27

2006

900

2.52

2273

952

2.80

2523

999

3.04

2744

4400

752

2.08

1840

800

2.21

1875

860

2.39

2110

912

2.66

2397

962

2.93

2642

1008

3.19

2885

4500

768

2.24

1980

814

2.35

1989

871

2.51

2265

924

2.80

2523

973

3.07

2772

1019

3.34

3029

4600

783

2.40

2119

827

2.50

2121

883

2.64

2380

937

2.95

2661

983

3.21

2904

4700

799

2.56

2309

841

2.64

2291

894

2.77

2496

949

3.10

2800

994

3.36

3049

4800

814

2.74

2469

855

2.80

2424

906

2.91

2624

961

3.26

2952

4900

868

2.90

2578

918

3.05

2754

972

3.40

3088

5000

883

3.10

2735

931

3.21

2904

580D120 (10 TONS)* (cont)

Airflow

(Cfm)

External Static Pressure (in. wg)

1.4

1.6

1.8

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3000

918

1.67

1482

967

1.89

1736

1010

2.09

1903

1063

2.46

2221

3100

928

1.78

1478

973

1.94

1778

1018

2.17

1971

1070

2.51

2265

3200

937

1.90

1745

981

2.04

1861

1026

2.26

2048

1075

2.57

2318

3300

946

2.00

1828

991

2.16

1963

1032

2.32

2099

1080

2.64

2380

3400

953

2.10

1912

1000

2.29

2074

1041

2.44

2203

1083

2.65

2389

3500

961

2.20

1997

1009

2.41

2177

1051

2.57

2318

1090

2.74

2469

3600

970

2.32

2099

1017

2.53

2282

1061

2.72

2451

1099

2.88

2596

3700

980

2.45

2212

1024

2.64

2380

1069

2.87

2587

1109

3.03

2735

3800

989

2.58

2326

1033

2.76

2487

1077

2.99

2698

1118

3.20

2895

3900

1000

2.73

2460

1042

2.91

2624

1085

3.12

2819

1127

3.36

3049

4000

1010

2.87

2587

1052

3.06

2763

1093

3.24

2933

4100

1021

3.02

2726

1062

3.22

2914

1102

3.41

3097

4200

1032

3.17

2866

1072

3.38

2971

4300

1042

3.32

3010

4400

4500

4600

4700

4800

4900

5000

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor
*Standard motor drive range is 685 to 935 rpm. Alternate motor drive

range is 835 to 1085 rpm. All other rpms require a field-supplied drive.

NOTES:
1. Boldface indicates field-supplied motor and drive are required.
2. Values include losses for filters, unit casing, and wet coils. See

page 52 for accessory/FIOP static pressure information.

3. Maximum continuous bhp is 2.4 for the standard motor and 2.9 for

the alternate motor. Maximum continuous watts are 2120 for the
standard motor and 2615 for the alternate motor. Extensive motor
and electrical testing on these units ensures that the full range of the
motor can be utilized with confidence. Using your fan motors up to
the wattage ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected. See
Evaporator-Fan Motor Performance table on page 55 for additional
information.

4. Use of a field-supplied motor may affect wire sizing. Contact your

local representative for details.

5. Interpolation is permissible. Do not extrapolate.

45

Advertising