Bryant 580D User Manual

Page 19

Advertising
background image

BASE UNIT DIMENSIONS — 579F180,216

UNIT
579F

DIMENSIONS

X

Y

Z

ft-in.

mm

ft-in.

mm

ft-in.

mm

180

3-2

965

4-0

1219

1-10

559

216

3-7

1090

3-2

965

1- 8

508

UNIT
579F

CORNER WEIGHT*

A

B

C

D

lb

kg

Lb

kg

lb

kg

lb

kg

180

384

174

370

168

358

162

538

244

216

520

235

508

230

486

220

636

288

*Weights are for unit only (aluminum plate fins) and do not in-

clude options or crating.

NOTES:
1. Dimensions in (

) are in millimeters.

2.

Center of gravity.

3.

Direction of airflow.

4. Ductwork to be attached to accessory roof curb or adapter only.
5. Minimum clearance:

a. Rear: 7

Ј

0

Љ

(2134) for coil removal. This dimension can be re-

duced to 4

Ј

0

Љ

(1219) if conditions permit coil removal from

the top.

b. Left side: 4

Ј

0

Љ

(1219) for proper condenser coil airflow.

c. Front: 4

Ј

0

Љ

(1219) for control box access.

d. Right side: 4

Ј

0

Љ

(1219) for proper operation of damper and

power exhaust (if so equipped).

e. Top: 6

Ј

0

Љ

(1829) to assure proper condenser fan operation.

f. Local codes or jurisdiction may prevail.

6. With the exception of clearance for the condenser coil and the

damper/power exhaust as stated in Note No. 5, a removable
fence or barricade requires no clearance.

7. Dimensions are from outside of corner post. Allow 0

Ј

-

5

16

Љ

(8) on

each side for top panel drip edge.

8. Do not locate adjacent units with flue discharge facing econo-

mizer inlet.