Bryant 580D User Manual

Page 32

Advertising
background image

PERFORMANCE DATA (cont)

FAN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont)

580D048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE)

Airflow

(Cfm)

Low Speed

High Speed

208 V

230, 460, 575 V

208 V

230, 460, 575 V

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

1200

0.68

0.41

458

0.74

0.45

506

0.74

0.51

572

0.85

0.56

632

1300

0.61

0.42

471

0.67

0.46

521

0.66

0.52

589

0.78

0.58

651

1400

0.53

0.45

503

0.59

0.49

556

0.59

0.54

616

0.70

0.60

681

1500

0.45

0.47

536

0.51

0.52

593

0.52

0.56

631

0.63

0.62

698

1600

0.36

0.49

557

0.42

0.54

616

0.45

0.58

654

0.56

0.64

723

1700

0.26

0.52

584

0.32

0.57

646

0.37

0.60

678

0.48

0.66

750

1800

0.15

0.54

610

0.22

0.60

674

0.30

0.62

698

0.41

0.68

772

1900

0.04

0.56

629

0.11

0.62

696

0.23

0.64

720

0.34

0.70

796

2000

0.16

0.66

744

0.26

0.73

823

LEGEND

Bhp

Brake Horsepower Input to Fan

Esp

External Static Pressure (in. wg)

FIOP — Factory-Installed Option

NOTES:
1. Values include losses for filters, unit casing, and wet coils. See

page 52 for accessory/FIOP static pressure information.

2. Extensive motor and electrical testing on these units ensures that the

full range of the motor can be utilized with confidence. Using your fan
motors up to the wattage ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
See Evaporator-Fan Motor Performance table on page 55 for addi-
tional information.

3. Use of a field-supplied motor may affect wire sizing. Contact your

local representative for details.

580D048 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)*

Airflow

(Cfm)

External Static Pressure (in. wg)

0.1

0.2

0.3

0.4

0.6

0.7

0.8

Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts

1200

596 0.20

210

665 0.25

263

722 0.31

320

779 0.36

378

872 0.48

504

915 0.54

567

957 0.60

630

1300

633 0.24

252

699 0.30

315

754 0.36

378

809 0.42

441

902 0.55

578

943 0.61

641

984 0.67

704

1400

672 0.30

315

735 0.36

378

788 0.42

441

840 0.48

504

933 0.62

651

972 0.69

720 1011 0.75

788

1500

711

0.35

368

770 0.42

441

822 0.49

510

873 0.55

578

963 0.69

725 1002 0.77

804 1041 0.84

858

1600

751 0.42

441

835 0.49

515

871 0.56

588

907 0.63

662

993 0.77

787 1033 0.85

869 1072 0.93

950

1700

791 0.49

515

873 0.57

599

907 0.65

678

941 0.72

757 1024 0.87

889 1064 0.96

976 1103 1.04 1063

1800

831 0.58

609

881 0.66

693

929 0.74

772

976 0.81

851 1057 0.97

991 1095 1.06 1078 1132 1.14 1165

1900

872 0.67

704

919 0.75

788

965 0.84

877

1011 0.92

967 1091 1.08 1104 1127 1.17 1191 1162 1.25 1277

2000

913 0.77

809

958 0.86

904

1002 0.95

993

1046 1.03 1082 1125 1.21 1237 1160 1.30 1323 1195 1.38 1410

580D048 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)

Airflow

(Cfm)

External Static Pressure (in. wg)

0.9

1.0

1.1

1.2

1.4

1.6

1.8

Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts

1200

993 0.65

678 1028 0.69

725 1056 0.72

751 1083 0.74

778 1134 0.80

935 1185 0.88

965 1331 0.99 1000

1300

1021 0.74

772 1058 0.80

841 1090 0.85

888 1121 0.89

935 1171 0.94

988 1219 1.00

999 1268 1.10 1029

1400

1049 0.82

837 1086 0.89

885 1120 0.96

950 1153 1.00

976 1210 1.12 1071 1257 1.17 1105 1307 1.25 1190

1500

1077 0.92

922

1113 0.99

985 1147 1.06 1054 1180 1.13 1081 1241 1.27 1215 1295 1.37 1294 1339 1.43 1350

1600

1107 1.00

998 1141 1.09 1084 1174 1.17 1134 1207 1.25 1196 1269 1.40 1339 1326 1.54 1454 1376 1.65 1558

1700

1137 1.12 1128 1171 1.20 1194 1203 1.29 1278 1235 1.37 1310 1296 1.53 1463 1354 1.70 1605 1407 1.84 1738

1800

1167 1.23 1239 1202 1.32 1313 1233 1.41 1398 1263 1.49 1425 1323 1.67 1597 1381 1.85 1747 1436 2.02 1907

1900

1197 1.35 1360 1232 1.45 1442 1263 1.54 1532 1294 1.63 1559 1351 1.81 1731 1408 2.00 1889 1463 2.19 2068

2000

1229 1.48 1491 1262 1.58 1572 1294 1.68 1671 1325 1.78 1702 1362 1.97 1884 1436 2.16 2040 1489 2.36 2229

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor
*Motor drive range is 835 to 1185 rpm. All other rpms require a field-

supplied drive.

NOTES:
1. Boldface indicates field-supplied motor and drive are required.
2. Values include losses for filters, unit casing, and wet coils. See

page 52 for accessory/FIOP static pressure information.

3. Maximum continuous bhp is 1.0, and the maximum continuous watts

are 1000. Extensive motor and electrical testing on these units en-
sure that the full range of the motor can be utilized with confidence.
Using your fan motors up to the wattage ratings shown will not result
in nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 55 for additional information.

4. Use of a field-supplied motor may affect wire sizing. Contact your

local representative for details.

5. Interpolation is permissible. Do not extrapolate.

32