GUIDE SPECIFICATIONS — 580D036-150 (cont)

b. Damper shall close upon indoor (evaporator) fan

shutoff.

c. Designed to close damper during loss of power

situations.

d. Equipped with 15% barometric relief damper.

*

5. 25% Two-Position Damper:

a. Two-position damper package shall include single

blade damper and motor. Admits up to 25% out-
door air.

b. Damper shall close upon indoor (evaporator) fan

shutoff.

c. Designed to close damper during loss of power

situations.

d. Equipped with barometric relief damper.

*

6. Solid-State Enthalpy Control:

a. For use with variable sliding plate economizer

package only.

b. Capable of sensing outdoor-air heat content (tem-

perature and humidity) and control economizer
cut-in point to have minimum heat content air
passing over the evaporator coil for most efficient
system operation.

*

7. Differential Enthalpy Sensor:

a. For use with economizer only.

b. Capable of comparing heat content (temperature

and humidity) of outdoor air and return air and
controlling economizer cut-in point at the most
economical level.

*

8. Head Pressure Control Package:

Consists of solid-state control and condenser-coil
temperature sensor to maintain condensing tem-
perature between 90 F and 110 F at outdoor ambient
temperatures down to −20 F by condenser-fan speed
modulation or condenser-fan cycling.

9. LP (Liquid Propane) Gas Conversion Kit:

Package shall contain all the necessary hardware
and instructions to convert a standard natural gas
unit for use with liquefied propane gas.

*

10. Commercial Programmable Thermostat:

Seven-day commercial progammable thermostat
shall be capable of auto-changeover, F/C, 3-stage
heating and 2-stage cabling. Thermostat shall also
be equipped with complete system status display.

*

11. Flue Shield:

Provides protection from the hot sides of the gas flue
hood.

*

12. Thermostat and Subbase:

Provides staged cooling and heating automatic (or
manual) changeover, fan control, and indicator light.

*

13. Condenser Coil Hail Guard Assembly:

Hail guard shall protect against damage from hail
and flying debris.

14. NO

x

Reduction Kit:

Package shall contain all necessary hardware and
instructions to convert a standard natural gas unit to
reduce the nitrous oxide (NOx) emissions to a level

of 40 nanograms/joule or less for unit sizes 036-060
being installed in California Air Quality Management
Districts.

15. Controls Upgrade Kit:

Kit shall contain high-pressure, loss-of-charge/low-
pressure, and freeze protection switches. It shall
mount on factory-installed Schrader fittings.

16. Alternate Motor(s) and/or Drive(s) (036-060, 090,

120, 150):

Alternate motor(s) and drive(s) shall be factory-
installed to provide additional performance range.

17. Flue Discharge Deflector:

Flue discharge deflector directs unit exhaust verti-
cally instead of horizontally.

*

18. Condenser Coil Grille:

The grille protects the condenser coil from damage
by large objects without increasing unit clearances.

19. Compressor Cycle Delay:

Unit shall be prevented from restarting for minimum
of 5 min. after shutdown.

20. Thru-the-Bottom Service Connectors:

Kit shall provide connectors to permit gas and elec-
trical connections to be brought to the unit through
the basepan.

21. Fan/Filter Status Switch:

Provides status of indoor (evaporator) fan (ON/OFF)
or filter (CLEAN/DIRTY). Status shall be displayed
over communication bus when used with direct
digital controls or with an indicator light at the
thermostat.

69