Bryant 580D User Manual

Page 8

Advertising
background image

PHYSICAL DATA — 580D036-072

UNIT SIZE 580D

036

048

060

072

NOMINAL CAPACITY (tons)

3

4

5

6

OPERATING WEIGHT (lb)

Unit

Al/Al*

460

470

490

565

Al/Cu*

465

476

497

576

Cu/Cu*

468

482

505

587

Economizer

Durablade

34

34

34

34

Parablade

42

42

42

42

Roof Curb†

115

115

115

115

COMPRESSOR

Hermetic

Quantity

1

1

1

1

No. Cylinders (per Circuit)

2

2

2

2

Oil (oz)

50

50

50

54

REFRIGERANT TYPE

R-22

Expansion Device

Acutrol™ Feed Device

Operating Charge (lb-oz)

Circuit 1

3-6

4-11

5-13

7-8

Circuit 2

CONDENSER COIL

Enhanced Copper Tubes, Aluminum Lanced Fins

Rows...Fins/in.

1...17

1...17

1...17

2...17

Total Face Area (sq ft)

7.36

11.39

13.19

10.42

CONDENSER FAN

Propeller Type

Nominal Cfm

3500

4000

4000

4000

Quantity...Diameter (in.)

1...22.0

1...22.0

1...22.0

1...22.0

Motor Hp...Rpm

1

4

...1100

1

4

...1100

1

4

...1100

1

4

...1100

Watts Input (Total)

325

325

325

325

EVAPORATOR COIL

Enhanced Copper Tubes, Aluminum Double-Wavy Fins

Rows...Fins/in.

2...15

2...15

3...15

4...15

Total Face Area (sq ft)

4.17

5.5

5.5

5.5

EVAPORATOR FAN

Centrifugal Type

Quantity...Size (in.)

Std

1...10 x 10

1...10 x 10

1...11 x 10

1...10 x 10

Alt

1...10 x 10

1...10 x 10

1...10 x 10

Type Drive

Std

Direct

Direct

Direct

Belt

Alt

Belt

Belt

Belt

Nominal Cfm

1200

1600

2000

2400

Motor Hp

Std

Alt

Maximum Continuous Bhp

Std

.34

.75

1.20

2.40

Alt

1.00

1.00

1.80

Motor Frame Size

Std

48

48

48

56

Alt

48

48

48

Nominal Rpm High/Low

Std

860/800

1075/970

1075/970

Alt

Fan Rpm Range

Std

1070-1460

Alt

760-1000

835-1185

900-1300

Motor Bearing Type

Ball

Ball

Ball

Ball

Maximum Allowable Rpm

2100

2100

2100

2100

Motor Pulley Pitch Diameter Min/Max (in.)

Std

2.8/3.8

Alt

1.9/2.9

1.9/2.9

2.4/3.4

Nominal Motor Shaft Diameter (in.)

Std

1

2

1

2

1

2

5

8

Alt

1

2

1

2

1

2

Fan Pulley Pitch Diameter (in.)

Std

4.5

Alt

4.5

4.0

4.5

Nominal Fan Shaft Diameter (in.)

Belt, Quantity...Type...Length (in.)

Std

1...A...40

Alt

1...A...34

1...A...34

1...A...39

Pulley Center Line Distance (in.)

Std

14.7-15.5

Alt

10.0-12.4

10.0-12.4

14.7-15.5

Speed Change per Full Turn of

Std

80

Movable Pulley Flange (rpm)

Alt

48

70

80

Movable Pulley Maximum Full Turns

Std

5

From Closed Position

Alt

5

5

5

Factory Setting

Std

3

Alt

3

3

3

Factory Speed Setting (rpm)

Std

1225

Alt

856

975

1060

Fan Shaft Diameter at Pulley (in.)

1

2

1

2

1

2

1

2

LEGEND

Al

Aluminum

Bhp — Brake Horsepower
Cu

Copper

*Evaporator coil fin material/condenser coil fin material. Contact your

local representative for details about coated fins.

†Weight of 14-in. roof curb.

**Rollout switch lockout is manually reset by interrupting power to unit

or resetting thermostat.

††Requires an optional or accessory Controls Upgrade Kit.

NOTE: The 580D036-150 units have a loss-of-charge/low-pressure
switch (accessory or option) located in the liquid line.

8