PERFORMANCE DATA (cont)

FAN PERFORMANCE — 579F180-300 UNITS (cont)

579F240 (20 TONS)*

Airflow

(Cfm)

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

6000

767

1.80

1617

858

2.20

1932

944

2.50

2256

1026

2.90

2600

1104

3.30

2967

1181

3.80

3358

6500

817

2.20

1992

903

2.60

2329

985

3.00

2673

1062

3.40

3031

1136

3.80

3410

1209

4.30

3811

7000

869

2.70

2427

950

3.10

2787

1028

3.50

3151

1102

3.90

3527

1172

4.40

3919

1241

4.80

4331

7500

920

3.30

2919

998

3.70

3303

1073

4.10

3689

1143

4.60

4083

1210

5.00

4490

1275

5.50

4914

8000

973

3.90

3476

1047

4.30

3886

1119

4.80

4294

1186

5.30

4708

1250

5.70

5131

1313

6.20

5569

8500

1026

4.60

4102

1097

5.10

4635

1166

5.60

4967

1231

6.00

5401

1292

6.50

5843

1352

7.00

6297

9000

1079

5.40

4800

1147

5.90

5257

1214

6.40

5714

1276

6.90

6171

1336

7.40

6632

1393

7.90

7102

9500

1133

6.20

5576

1199

6.80

6058

1263

7.30

6540

1323

7.90

7018

1381

8.40

7500

1436

8.90

7988

10,000

1188

7.20

6432

1250

7.80

6939

1313

8.30

7444

1371

8.90

7946

1426

9.50

8449

579F240 (20 TONS)* (cont)

Airflow

(Cfm)

External Static Pressure (in. wg)

1.4

1.6

1.8

1.9

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

6000

1255

4.20

3772

1327

4.70

4206

1396

5.20

4658

1431

5.45

4884

1465

5.70

5110

6500

1279

4.70

4233

1348

5.20

4677

1415

5.80

5139

1449

6.10

5370

1482

6.40

5601

7000

1308

5.30

4762

1373

5.80

5215

1437

6.40

5686

1469

6.70

5922

1501

7.00

6157

7500

1339

6.00

5356

1401

6.50

5818

1462

7.00

6298

1493

7.25

6538

1523

7.50

6778

8000

1373

6.70

6024

1433

7.30

6495

1493

7.80

6966

1523

8.05

7202

8500

1410

7.60

6765

1467

8.10

7248

1524

8.70

7731

9000

1449

8.50

7584

1503

9.00

8033

9500

1488

9.40

8403

10,000

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

*Standard low-medium static motor drive range is 1002 to 1225 rpm. Al-

ternate high static motor drive range is 1193 to 1458 rpm. Other rpms
require a field-supplied drive.

NOTES:
1. Static pressure losses (i.e., economizer) must be added to exter-

nal static pressure before entering Fan Performance table. See
Accessory/FIOP Static Pressure table on page 52 for more
information.

2. Interpolation is permissible. Do not extrapolate.
3. Maximum continuous bhp is 8.7 for 208/230-v units and 9.5 for 460-v

units. The maximum continuous watts are 7915 for the 208/230-v
units and 8640 for the 460-v units. Extensive motor and drive testing
on these units ensures that the full horsepower range of the motor
can be utilized with confidence. Using your fan motors up to the
watts rating shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.

4. Deduct 0.2 in. wg static pressure for high heat units at or above

9000 cfm. Deduct 0.3 in. wg static pressure for high heat units at or
above 10,000 cfm.