PERFORMANCE DATA (cont)

FAN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont)

580D120 (10 TONS)*

Airflow

(Cfm)

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3000

592

0.76

723

661

0.93

859

722

1.09

989

779

1.26

1131

829

1.42

1267

880

1.58

1404

3100

607

0.83

779

676

1.01

924

734

1.17

1056

791

1.34

1199

840

1.51

1344

890

1.68

1491

3200

622

0.90

835

690

1.09

989

746

1.25

1123

803

1.43

1275

852

1.60

1422

900

1.77

1569

3300

638

0.98

899

705

1.17

1056

759

1.33

1190

815

1.52

1353

864

1.70

1508

910

1.88

1665

3400

653

1.06

965

719

1.26

1131

772

1.43

1275

826

1.62

1439

876

1.81

1604

921

1.98

1753

3500

669

1.15

1039

733

1.35

1207

786

1.53

1361

838

1.72

1526

888

1.91

1691

933

2.10

1858

3600

684

1.24

1114

747

1.44

1284

800

1.64

1456

850

1.82

1613

900

2.03

1796

945

2.22

2014

3700

700

1.33

1190

760

1.54

1370

814

1.75

1552

863

1.92

1700

912

2.14

1892

957

2.34

2117

3800

715

1.43

1275

774

1.64

1456

828

1.86

1648

875

2.04

1805

924

2.26

1997

969

2.47

2230

3900

731

1.54

1370

787

1.74

1543

843

1.98

1753

888

2.16

1910

936

2.38

2151

981

2.60

2344

4000

747

1.64

1456

801

1.85

1639

857

2.10

1858

902

2.30

2032

948

2.51

2265

993

2.74

2469

4100

763

1.76

1560

816

1.97

1744

872

2.23

1971

916

2.44

2203

960

2.64

2380

1005

2.88

2596

4200

778

1.88

1665

831

2.10

1884

886

2.36

2084

929

2.58

2326

972

2.78

2505

1016

3.03

2735

4300

794

2.00

1770

846

2.23

1971

900

2.50

2256

943

2.73

2460

985

2.93

2642

1028

3.17

2866

4400

810

2.13

1884

861

2.37

2093

913

2.64

2380

958

2.89

2605

999

3.09

2791

1040

3.32

3010

4500

826

2.27

2006

876

2.52

2273

927

2.78

2505

973

3.04

2744

1012

3.26

2952

4600

842

2.41

2177

892

2.67

2406

940

2.92

2633

987

3.21

2904

4700

858

2.55

2300

907

2.83

2551

954

3.08

2782

1002

3.38

3068

4800

874

2.70

2433

922

2.99

2698

968

3.24

2933

4900

890

2.86

2578

938

3.16

2857

5000

906

3.03

2735

953

3.33

3020

580D120 (10 TONS)* (cont)

Airflow

(Cfm)

External Static Pressure (in. wg)

1.4

1.6

1.8

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3000

924

1.73

1534

970

1.89

1736

1019

2.00

1828

1066

2.30

2082

3100

935

1.84

1695

977

2.00

1828

1026

2.17

1971

1070

2.44

2203

3200

946

1.95

1786

987

2.11

1920

1029

2.28

2065

1075

2.51

2265

3300

957

2.06

1878

998

2.23

2022

1037

2.40

2169

1082

2.58

2326

3400

967

2.17

1971

1009

2.35

2125

1047

2.53

2282

1087

2.70

2433

3500

976

2.29

2074

1020

2.48

2238

1058

2.66

2397

1095

2.84

2560

3600

986

2.41

2177

1030

2.61

2353

1069

2.80

2523

1106

2.98

2688

3700

998

2.54

2291

1039

2.74

2469

1081

2.94

2651

1117

3.13

2829

3800

1010

2.67

2406

1049

2.87

2587

1091

3.08

2782

1128

3.29

2981

3900

1022

2.81

2533

1060

3.02

2726

1100

3.23

2923

4000

1034

2.96

2670

1072

3.17

2866

1110

3.38

3068

4100

1046

3.11

2810

1084

3.32

3010

4200

1058

3.26

2952

4300

4400

4500

4600

4700

4800

4900

5000

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor
*Standard motor drive range is 685 to 935 rpm. Alternate motor drive

range is 835 to 1085 rpm. All other rpms require a field-supplied drive.

NOTES:
1. Boldface indicates field-supplied motor and drive are required.
2. Values include losses for filters, unit casing, and wet coils. See

page 52 for accessory/FIOP static pressure information.

3. Maximum continuous bhp is 2.4 for the standard motor and 2.9 for

the alternate motor. Maximum continuous watts are 2120 for the
standard motor and 2615 for the alternate motor. Extensive motor
and electrical testing on these units ensures that the full range of the
motor can be utilized with confidence. Using your fan motors up to
the wattage ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected. See
Evaporator-Fan Motor Performance table on page 55 for additional
information.

4. Use of a field-supplied motor may affect wire sizing. Contact your

local representative for details.

5. Interpolation is permissible. Do not extrapolate.