Bryant 580D User Manual

Page 30

Advertising
background image

PERFORMANCE DATA (cont)

COOLING CAPACITIES (cont)

579F240 (20 TONS)

Temp (F)

Air Entering

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

6000/0.06

7000/0.07

8000/0.08

9000/0.09

10,000/0.10

Air Entering Evaporator — Ewb (F)

72

67

62

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

274.0

250.0

226.0

280.0

256.0

232.0

284.0

260.0

236.0

288.0

264.0

242.0

292.0

268.0

246.0

SHC

130.4

163.6

194.4

136.4

175.0

210.0

144.4

186.8

224.0

151.8

197.0

236.0

157.4

208.0

246.0

kW

16.92

16.40

15.90

17.04

16.58

16.12

17.22

16.72

16.22

17.32

16.84

16.36

17.42

16.92

16.50

85

TC

264.0

240.0

216.0

270.0

244.0

222.0

276.0

250.0

226.0

278.0

254.0

232.0

282.0

256.0

238.0

SHC

127.6

159.8

189.8

138.2

172.2

206.0

141.8

183.4

220.0

147.8

194.6

232.0

154.6

204.0

236.0

kW

18.54

18.00

17.36

18.72

18.18

17.60

18.96

18.34

17.74

19.04

18.46

17.94

19.14

18.56

18.08

95

TC

252.0

228.0

204.0

258.0

234.0

210.0

262.0

238.0

216.0

266.0

240.0

222.0

270.0

242.0

228.0

SHC

124.4

155.4

184.6

131.0

167.6

200.0

138.8

178.8

214.0

145.2

189.8

222.0

151.8

200.0

228.0

kW

20.20

19.52

18.82

20.40

19.76

19.08

20.60

19.90

19.28

20.80

20.00

19.52

20.80

20.20

19.76

105

TC

240.0

216.0

190.6

246.0

222.0

196.6

250.0

226.0

204.0

252.0

228.0

212.0

256.0

230.0

218.0

SHC

120.0

150.8

178.4

127.2

163.6

193.8

135.0

175.2

204.0

141.6

185.4

212.0

147.4

196.2

218.0

kW

21.80

21.00

20.20

22.00

21.20

20.60

22.20

21.40

20.80

22.40

21.60

21.00

22.40

21.60

21.40

115

TC

228.0

204.0

176.6

232.0

208.0

184.6

236.0

212.0

194.2

238.0

214.0

202.0

240.0

216.0

208.0

SHC

116.0

146.2

171.8

123.8

158.4

184.6

130.4

169.6

194.2

137.2

180.8

202.0

144.0

190.8

206.0

kW

23.40

22.40

21.60

23.60

22.60

22.00

23.80

22.80

22.40

23.80

23.00

22.60

24.00

23.20

22.80

125

TC

214.0

188.8

163.2

218.0

194.2

174.2

220.0

197.6

183.4

224.0

199.8

190.6

226.0

202.0

196.0

SHC

111.0

140.8

162.8

118.6

153.4

174.2

125.8

164.8

183.4

132.0

175.6

190.4

139.0

185.2

195.4

kW

24.80

23.80

23.00

25.00

24.00

23.40

25.20

24.20

23.80

25.40

24.40

24.00

25.40

24.60

24.40

579F300 (25 TONS)

Temp (F)

Air Entering

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

7000/0.03

8750/0.05

10,000/0.07

11,250/0.09

Air Entering Evaporator — Ewb (F)

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

323.9

299.4

275.8

331.3

312.7

288.4

336.1

319.8

294.7

342.6

322.5

300.0

SHC

159.4

195.2

230.6

170.1

216.5

259.1

177.6

231.1

276.8

186.6

242.9

292.6

kW

21.10

20.50

19.90

21.30

20.90

20.20

21.50

21.10

20.40

21.70

21.20

20.50

85

TC

315.3

290.4

264.3

326.9

303.2

278.0

333.7

309.1

285.0

335.1

314.2

291.1

SHC

156.3

191.7

224.9

168.4

213.2

254.9

177.5

226.9

273.8

184.4

240.7

288.4

kW

22.70

22.10

21.30

23.10

22.50

21.80

23.30

22.70

22.00

23.30

22.80

22.20

95

TC

304.1

277.4

243.1

315.3

290.1

263.8

320.4

295.6

271.1

324.1

300.6

279.4

SHC

152.0

186.5

215.2

165.0

208.5

248.0

173.0

222.4

266.4

181.6

236.5

279.4

kW

24.80

24.00

23.20

25.20

24.50

23.50

25.40

24.60

23.80

25.50

24.80

24.10

105

TC

291.2

261.4

224.8

300.9

274.2

242.1

305.7

280.3

252.3

309.8

284.8

266.3

SHC

147.2

179.7

206.6

159.9

201.8

237.3

168.3

216.8

252.3

176.8

231.1

266.3

kW

26.90

25.80

25.00

27.20

26.30

25.40

27.40

26.60

25.80

27.60

26.80

26.00

115

TC

274.6

237.9

207.6

285.9

251.5

222.6

291.3

258.4

237.7

293.9

267.5

247.1

SHC

140.9

170.0

198.6

154.9

193.2

222.6

164.1

208.7

237.7

163.0

224.3

247.1

kW

28.80

27.80

26.80

29.40

28.20

27.40

29.60

28.50

27.70

29.70

28.50

28.10

125

TC

254.5

214.9

184.3

266.7

230.9

206.7

272.0

236.0

220.8

276.1

240.0

231.1

SHC

133.3

160.8

184.3

148.0

185.1

206.7

157.5

200.2

220.8

166.6

214.4

231.1

kW

30.90

29.90

28.90

31.40

30.20

29.60

31.70

30.50

29.90

31.90

30.80

30.30

Standard Ratings

LEGEND

BF

Bypass Factor

Edb

Entering Dry-Bulb

Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

Ldb

Leaving Dry-Bulb

Lwb — Leaving Wet-Bulb
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

sensible capacity (Btuh)

tldb = tedb −

1.10 x cfm

tlwb = Wet-bulb temperature corresponding to enthalpy of air leav-

ing evaporator coil (hlwb)

total capacity (Btuh)

hlwb = hewb −

4.5 x cfm

Where: hewb = Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evapo-

rator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82

Interpolation is permissible.
Correction Factor = 1.10 x (1 − BF) x (edb − 80).

30