PERFORMANCE DATA (cont)

FAN PERFORMANCE — 579F180-300 UNITS (cont)

579F216 (18 TONS)*

Airflow

(Cfm)

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

5000

669

1.10

1019

772

1.40

1291

870

1.80

1582

963

2.10

1903

1052

2.50

2251

1137

2.90

2623

5500

717

1.40

1292

813

1.80

1585

905

2.10

1892

992

2.50

2223

1076

2.90

2680

1157

3.30

2962

6000

767

1.80

1617

858

2.20

1932

944

2.50

2256

1026

2.90

2600

1104

3.30

2967

1181

3.80

3358

6500

817

2.20

1992

903

2.60

2329

985

3.00

2673

1062

3.40

3031

1136

3.80

3410

1209

4.30

3811

7000

869

2.70

2427

950

3.10

2787

1028

3.50

3151

1102

3.90

3527

1172

4.40

3919

1241

4.80

4331

7200

889

2.94

2624

969

3.34

2993

1046

3.74

3366

1118

4.18

3749

1187

4.64

4147

1255

5.08

4564

7500

920

3.30

2919

998

3.70

3303

1073

4.10

3689

1143

4.60

4083

1210

5.00

4490

1275

5.50

4914

8000

973

3.90

3476

1047

4.30

3886

1119

4.80

4294

1186

5.30

4708

1250

5.70

5131

8500

1026

4.60

4102

1097

5.10

4635

1166

5.60

4967

9000

1079

5.40

4800

579F216 (18 TONS)* (cont)

Airflow

(Cfm)

External Static Pressure (in. wg)

1.3

1.4

1.6

1.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

5000

1178

3.15

2820

1218

3.40

3016

1295

3.80

3425

1369

4.30

3849

5500

1196

3.55

3164

1234

3.80

3366

1309

4.20

3789

1381

4.70

4229

6000

1218

4.00

3565

1251

4.20

3772

1327

4.70

4206

1396

5.20

4658

6500

1244

4.50

4022

1279

4.70

4233

1348

5.20

4677

1415

5.80

5139

7000

1275

5.05

4547

1308

5.30

4762

7200

1288

5.33

4783

7500

1307

5.75

5135

8000

8500

9000

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

*Standard low-medium static drive range is 817 to 1038 rpm. Alternate
high static high static motor drive range is 994 to 1197. Other rpms re-
quire a field-supplied drive.

NOTES:
1. Static pressure losses (i.e., economizer) must be added to exter-

nal static pressure before entering Fan Performance table. See
Accessory/FIOP Static Pressure table on page 52 for more
information.

2. Interpolation is permissible. Do not extrapolate.
3. Maximum continuous bhp is 5.9 and the maximum continuous watts

are 5180. Extensive motor and drive testing on these units ensures
that the full horsepower range of the motor can be utilized with con-
fidence. Using your fan motors up to the watts rating shown will not
result in nuisance tripping or premature motor failure. Unit warranty
will not be affected.

4. Deduct 0.2 in. wg static pressure for high heat units at or above

8000 cfm.

48