ARI* CAPACITY RATINGS (cont)

HEATING CAPACITIES AND EFFICIENCIES — 580D036-150

UNIT 580D

HEATING INPUT

(Btuh)

Stage 2/Stage 1

OUTPUT CAPACITY

(Btuh)

TEMPERATURE

RISE

(F)

AFUE

(%)

STEADY-STATE

EFFICIENCY

(%)

CALIFORNIA

SEASONAL

EFFICIENCY

(%)

036 074

—/ 72,000

59,200

25-55

80.0

80.0

77.2

036 115

115,000/ 82,000

92,000

55-85

80.0

80.0

76.7

048 074

—/ 72,000

59,200

25-55

80.0

80.0

77.2

048 115

—/115,000

92,000

35-65

80.0

80.0

77.1

048 150

150,000/120,000

120,000

50-80

80.0

80.0

76.9

060 074

—/ 72,000

59,200

25-55

80.0

80.0

77.2

060 115

—/115,000

92,000

35-65

80.0

80.0

77.1

060 150

150,000/120,000

120,000

50-80

80.0

80.0

76.9

072 074

—/ 72,000

59,200

25-55

80.0

80.0

77.2

072 115

—/115,000

92,000

35-65

80.0

80.0

77.1

072 150

150,000/120,000

120,000

50-80

80.0

80.0

76.9

090 125

—/125,000

100,000

20-50

80.0

80.0

75.8

090 180

180,000/120,000

144,000

35-65

80.0

80.0

77.1

090 224

224,000/180,000

179,200

45-75

80.0

80.0

77.1

102 125

—/125,000

100,000

20-50

80.0

80.0

75.8

102 184

180,000/120,000

144,000

35-65

80.0

80.0

77.1

102 224

224,000/180,000

179,200

45-75

80.0

80.0

77.1

120 180

180,000/120,000

144,000

35-65

80.0

80.0

77.1

120 224

224,000/180,000

179,200

35-65

80.0

80.0

77.1

120 250

250,000/200,000

200,000

40-70

80.0

80.0

76.4

150 224

224,000/180,000

179,200

35-65

80.0

80.0

77.1

150 250

250,000/200,000

200,000

40-70

80.0

80.0

76.4

LEGEND

AFUE — Annual Fuel Utilization Efficiency

NOTE: NOx levels are 40 nanograms/joule or less with the accessory NOx reduction kit (sizes 036-060).

HEATING CAPACITIES AND EFFICIENCIES — 579F180-300

UNIT 579F

HEATING INPUT

(Btuh)

Stage 2/Stage 1*

OUTPUT CAPACITY

(Btuh)

TEMPERATURE

RISE

(F)

STEADY-STATE

EFFICIENCY

(%)

MINIMUM

HEATING

CFM

180 230

230,000/172,000

186,000

15-45

81.0

3800

180 300

300,000/225,000

243,000

30-60

81.0

3800

216 275

275,000/206,000

223,000

15-45

81.0

4750

216 360

360,000/270,000

292,000

20-50

81.0

5450

240 275

275,000/206,000

223,000

15-45

81.0

4750

240 360

360,000/270,000

292,000

20-50

81.0

5450

300 275

275,000/206,000

223,000

15-45

81.0

4750

300 360

360,000/270,000

292,000

20-50

81.0

5450

*All units are 2-stage heat.

NOTE: Minimum allowable temperature of mixed-air entering the heat exchanger during first-stage
heating is 45 F. There is no minimum mixed-air temperature limitation during second-stage heating.
For entering-air temperatures below 45 F both stages of heat must be energized together to minimize
condensation issues and to ensure proper unit operation.