Bryant 580D User Manual

Page 52

Advertising
background image

PERFORMANCE DATA (cont)

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) − 580D036-072

COMPONENT

CFM

900

1200

1400

1600

1800

2000

2200

2400

2600

3000

Durablade Economizer

0.05

0.05

0.05

0.05

0.05

0.05

0.05

0.05

0.05

0.05

Parablade Economizer

0.08

0.10

0.17

0.26

0.33

0.34

0.36

0.40

0.44

LEGEND

FIOP − Factory-Installed Option
*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with

the Fan Performance tables to determine blower rpm and watts.

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) − 580D090-150

COMPONENT

CFM

2200

2500

3000

3500

4000

4500

5000

5500

6000

6250

Durablade Economizer

0.02

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.09

Parablade Economizer

0.21

0.25

0.35

0.49

0.61

LEGEND

FIOP − Factory-Installed Option
*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with

the Fan Performance tables to determine blower rpm and watts.

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) − 579F180-300

COMPONENT

CFM

4500

5000

5400

6000

7200

7500

9000

10,000

11,250

Economizer

0.04

0.05

0.06

0.07

0.09

0.10

0.11

0.12

0.14

LEGEND

FIOP − Factory-Installed Option
*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with

the Fan Performance tables to determine blower rpm and watts.

FAN RPM AT MOTOR PULLEY SETTINGS* — 580D036-150 AND 579F180-300

UNIT

MOTOR PULLEY TURNS OPEN

0

1

2

1

1

1

2

2

2

1

2

3

3

1

2

4

4

1

2

5

5

1

2

6

580D036†

1000

976

952

928

904

880

856

832

808

784

760

580D048†

1185

1150

1115

1080

1045

1010

975

940

905

870

835

580D060†

1300

1260

1220

1180

1140

1100

1060

1020

980

940

900

580D072**

1460

1420

1380

1345

1305

1265

1225

1185

1150

1110

1070

580D090**

840

815

790

765

740

715

690

665

635

615

590

580D090††

935

910

885

860

835

810

785

760

735

710

685

580D102**

935

910

885

860

835

810

785

760

735

710

685

580D120**

935

910

885

860

835

810

785

760

735

710

685

580D120†

1085

1060

1035

1010

985

960

935

910

885

860

835

580D150**

1080

1060

1035

1015

990

970

950

925

905

880

860

580D150†

1260

1220

1185

1155

1130

1100

1075

1045

1015

990

960

930

900

579F180**

1179

1150

1121

1093

1064

1035

1006

978

949

920

891

579F180††

1559

1522

1488

1455

1422

1389

1356

1323

1289

1256

1227

579F216**

1038

1023

1001

979

956

934

912

890

868

846

817

579F216††

1197

1185

1165

1145

1124

1104

1084

1064

1043

1023

994

579F240**

1225

1209

1187

1165

1143

1120

1098

1076

1053

1031

1022

579F240††

1458

1434

1407

1381

1354

1328

1301

1275

1248

1222

1193

579F300**

1283

1269

1247

1225

1203

1182

1160

1138

1116

1095

1066

579F300††

N/A

N/A

1551

1524

1497

1470

1443

1415

1388

1361

1332

*Approximate fan rpm shown.

†Indicates alternate motor and drive package.

**Indicates standard motor and drive package.

††Indicates alternate drive package only.

Due to belt and pulley size, pulley cannot be set to this number of turns open.

52

Advertising