PERFORMANCE DATA (cont)

FAN PERFORMANCE — 580D036-150 HORIZONTAL DISCHARGE UNITS (cont)

580D090 (7

1

2

TONS)*

Airflow

(Cfm)

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

0.9

1.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

2250

507

0.53

547

586

0.73

700

658

0.97

891

722

1.22

1097

752

1.34

1199

783

1.46

1301

2300

513

0.55

562

592

0.76

723

663

1.00

916

727

1.26

1131

756

1.38

1224

786

1.49

1327

2400

528

0.60

600

606

0.83

779

674

1.06

965

738

1.34

1199

766

1.46

1301

795

1.58

1404

2500

542

0.66

646

619

0.90

835

686

1.13

1022

748

1.41

1258

777

1.55

1370

806

1.68

1491

2550

550

0.69

669

627

0.94

867

692

1.17

1056

754

1.45

1292

783

1.60

1413

812

1.74

1543

2600

557

0.72

692

634

0.97

891

698

1.21

1089

759

1.49

1327

787

1.64

1456

816

1.79

1587

2700

573

0.79

747

648

1.05

956

711

1.29

1156

770

1.58

1404

798

1.73

1534

827

1.88

1665

2800

588

0.86

803

662

1.13

1022

723

1.38

1233

782

1.66

1473

809

1.82

1613

837

1.98

1753

2900

604

0.94

867

676

1.21

1089

737

1.48

1318

794

1.76

1560

821

1.92

1700

848

2.08

1840

3000

620

1.02

932

690

1.30

1165

750

1.58

1404

806

1.86

1648

832

2.02

1788

849

2.18

1927

3100

636

1.11

1006

704

1.39

1241

764

1.69

1499

818

1.97

1744

844

2.13

1884

870

2.29

2023

3200

652

1.21

1089

718

1.49

1327

778

1.80

1595

831

2.09

1849

856

2.25

1980

882

2.40

2119

3300

668

1.31

1173

732

1.59

1413

793

1.92

1700

844

2.21

1954

869

2.37

2093

894

2.53

2232

3400

684

1.41

1258

747

1.70

1508

807

2.04

1805

857

2.35

2076

882

2.51

2206

907

2.66

2343

3500

701

1.53

1361

762

1.82

1613

821

2.16

1910

871

2.48

2188

895

2.64

2326

919

2.80

2462

3600

717

1.65

1465

777

1.94

1718

835

2.29

2023

885

2.63

2317

908

2.79

2453

932

2.95

2587

3700

733

1.77

1569

792

2.07

1831

849

2.42

2136

899

2.78

2445

922

2.95

2579

945

3.11

2718

3750

742

1.84

1630

800

2.14

1892

856

2.49

2197

907

2.86

2512

929

3.03

2653

952

3.20

2719

580D090 (7

1

2

TONS)* (cont)

Airflow

(Cfm)

External Static Pressure (in. wg)

1.2

1.4

1.6

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

2250

843

1.81

1604

908

2.25

1989

955

2.59

2283

2300

846

1.84

1630

910

2.25

2015

959

2.61

2300

2400

853

1.88

1665

912

2.31

2041

967

2.68

2360

2500

859

1.94

1718

919

2.37

2093

971

2.73

2403

2550

864

1.99

1761

920

2.39

2110

974

2.76

2428

2600

868

2.04

1805

921

2.41

2136

976

2.78

2445

2700

878

2.16

1910

928

2.45

2162

983

2.88

2529

2800

889

2.29

2023

937

2.57

2266

986

2.91

2554

2900

900

2.41

2128

947

2.70

2377

993

3.01

2637

3000

910

2.52

2223

958

2.85

2504

1002

3.15

2751

3100

920

2.64

2326

968

2.99

2620

1012

3.30

2870

3200

931

2.76

2428

979

3.13

2735

1023

3.47

3002

3300

942

2.89

2537

989

3.26

2839

1034

3.63

3121

3400

954

3.02

2645

1000

3.40

2948

1044

3.79

3237

3500

966

3.15

2751

1011

3.55

3062

1054

3.94

3340

3600

978

3.30

2870

1022

3.69

3165

1065

4.10

3445

3700

990

3.45

2987

1034

3.84

3272

1076

4.26

3544

3750

997

3.54

3055

1040

3.93

3333

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor
*Standard drive range is 590 to 840 rpm. Alternate drive range is 685 to

935 rpm. All other rpms require a field-supplied drive.

NOTES:
1. Boldface indicates field-supplied motor and drive are required.
2. Values include losses for filters, unit casing, and wet coils. See

page 52 for accessory/FIOP static pressure information.

3. Maximum continuous bhp is 2.4 and maximum continuous watts are

2120. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. See Evaporator-Fan Motor Performance table on page 55
for additional information.

4. Use of a field-supplied motor may affect wire sizing. Contact your

local representative for details.

5. Interpolation is permissible. Do not extrapolate.