PERFORMANCE DATA (cont)

FAN PERFORMANCE — 579F180-300 UNITS (cont)

579F300 (25 TONS)*

Airflow

(Cfm)

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

0.9

1.0

Rpm

Bhp

Watts Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts Rpm

Bhp

Watts

7,500

962

3.39

3123

1039

3.81

3507

1111

4.23

3895

1179

4.66

4295

1212

4.89

4503

1245

5.11

4710

8,000 1017

4.04

3717

1091

4.48

4126

1160

4.93

4536

1225

5.38

4954

1256

5.62

5170

1287

5.85

5386

8,500 1072

4.76

4385

1143

5.23

4818

1209

5.70

5250

1271

6.18

5688

1302

6.42

5913

1332

6.66

6137

9,000

1128

5.57

5129

1196

6.07

5587

1260

6.56

6042

1320

7.06

6501

1348

7.32

6735

1377

7.57

6968

9,500

1185

6.47

5955

1250

6.99

6437

1311

7.51

6915

1369

8.03

7395

1396

8.30

7638

1424

8.56

7881

10,000

1241

7.45

6865

1304

8.00

7372

1363

8.55

7873

1419

9.09

8376

1445

9.37

8629

1472

9.64

8882

10,500

1298

8.54

7865

1359

9.12

8396

1415

9.69

8921

1469 10.26

9446

1495 10.55

9710

1521 10.83

9973

11,000

1355

9.72

8956

1414 10.33

9512

1469 10.93 10,062 1521 11.52 10,609

11,250

1384 10.36

9540

1441 10.97 10,107 1495 11.58 10,668

579F300 (25 TONS)* (cont)

Airflow

(Cfm)

External Static Pressure (in. wg)

1.2

1.3

1.4

1.6

1.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

7,500

1309

5.58

5143

1341

5.83

5370

1372

6.08

5597

1434

6.59

6067

1494

7.12

6558

8,000

1349

6.33

5833

1379

6.59

6065

1409

6.84

6297

1467

7.36

6779

8,500

1390

7.17

6600

1419

7.43

6839

1447

7.68

7077

1504

8.22

7571

9,000

1433

8.08

7446

1461

8.35

7692

1488

8.62

7938

9,500

1478

9.10

8378

1505

9.37

8626

10,000

1524

10.20

9396

1550

10.48

9653

10,500

11,000

11,250

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

*Standard low-medium static motor drive range is 1066 to 1283 rpm. Al-

ternate high static motor drive range is 1332 to 1550 rpm. Other rpms
require a field-supplied drive.

NOTES:
1. Static pressure losses (i.e., economizer) must be added to exter-

nal static pressure before entering Fan Performance table. See
Accessory/FIOP Static Pressure table on page 52 for more
information.

2. Interpolation is permissible. Do not extrapolate.
3. Fan performance is based on wet coils, clean filters, and casing

losses.

4. Maximum continuous bhp is 10.2 for 208/230-v units and 11.8 for

460-v units. The maximum continuous watts are 9510 for the 208/
230-v units and 11,000 for the 460-v units. Extensive motor and drive
testing on these units ensures that the full horsepower range of the
motor can be utilized with confidence. Using your fan motors up to
the watts rating shown will not result in nuisance tripping or prema-
ture motor failure. Unit warranty will not be affected.

5. Deduct 0.3 in. wg static pressure for high heat units at or above

10,000 cfm.

50