PERFORMANCE DATA (cont)

FAN PERFORMANCE — 580D036-150 HORIZONTAL DISCHARGE UNITS (cont)

580D048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE)

Airflow

(Cfm)

Low Speed

High Speed

208 v

230, 460, 575 v

208 v

230, 460, 575 v

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

1200

0.75

0.41

458

0.81

0.45

506

0.87

0.51

572

0.92

0.56

632

1300

0.68

0.42

471

0.74

0.46

521

0.79

0.52

589

0.85

0.58

651

1400

0.60

0.45

503

0.66

0.49

556

0.71

0.54

616

0.77

0.60

681

1500

0.51

0.47

536

0.58

0.52

593

0.64

0.56

631

0.70

0.62

698

1600

0.42

0.49

557

0.49

0.54

616

0.56

0.58

654

0.63

0.64

723

1700

0.32

0.52

584

0.39

0.57

646

0.48

0.60

678

0.55

0.66

750

1800

0.21

0.54

610

0.29

0.60

674

0.41

0.62

698

0.48

0.68

772

1900

0.09

0.56

629

0.18

0.62

696

0.33

0.64

720

0.41

0.70

796

2000

0.06

0.65

731

0.26

0.66

744

0.33

0.73

823

LEGEND

Bhp

Brake Horsepower Input to Fan

Esp

External Static Pressure (in. wg)

FIOP — Factory-Installed Option

NOTES:
1. Values include losses for filters, unit casing, and wet coils. See

page 52 for accessory/FIOP static pressure information.

2. Extensive motor and electrical testing on these units ensures that the

full range of the motor can be utilized with confidence. Using your fan
motors up to the wattage ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
See Evaporator-Fan Motor Performance table on page 55 for addi-
tional information.

3. Use of a field-supplied motor may affect wire sizing. Contact your

local representative for details.

580D048 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)*

Airflow

(Cfm)

External Static Pressure (in. wg)

0.1

0.2

0.3

0.4

0.6

0.7

0.8

Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts

1200

569 0.18

189

641 0.23

242

701 0.29

299

761 0.34

357

859 0.46

483

901 0.52

546

943 0.58

609

1300

604 0.22

231

673 0.28

294

731 0.34

352

788 0.39

410

887 0.52

546

928 0.59

615

968 0.65

683

1400

640 0.27

284

705 0.33

347

761 0.39

410

817 0.45

473

914 0.59

620

955 0.66

688

996 0.72

757

1500

676 0.32

336

738 0.38

399

793 0.45

468

847 0.51

536

940 0.65

683

982 0.73

767 1024 0.81

851

1600

713 0.38

399

772 0.44

462

825 0.51

536

877 0.58

609

967 0.73

767 1009 0.81

851 1051 0.89

935

1700

750 0.45

473

806 0.51

536

857 0.59

615

908 0.66

693

997 0.81

851 1037 0.90

940 1077 1.01 1030

1800

788 0.52

546

841 0.59

620

890 0.67

704

939 0.75

788

1026 0.91

956 1065 1.01 1040 1104 1.07 1124

1900

826 0.60

630

876 0.68

714

924 0.76

799

971 0.84

883

1056 1.01 1061 1094 1.10 1151 1132 1.18 1240

2000

864 0.70

735

912 0.77

809

958 0.86

898

1004 0.94

988

1087 1.12 1177 1125 1.21 1271 1162 1.30 1366

580D048 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)

Airflow

(Cfm)

External Static Pressure (in. wg)

0.9

1.0

1.1

1.2

1.4

1.6

1.8

Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts

1200

987 0.64

652 1030 0.70

695 1068 0.79

792 1106 0.87

889 1134 0.98

998 1189 1.12

1138 1245 1.21 1358

1300

1006 0.71

709 1044 0.77

736 1086 0.84

833 1128 0.91

930 1183 1.10 1052 1226 1.23

1215 1297 1.35 1406

1400

1033 0.79

797 1069 0.86

838 1104 0.93

925 1139 1.01 1012 1218 1.14 1090 1286 1.34

1282 1320 1.48 1463

1500

1060 0.88

891 1095 0.95

930 1129 1.02 1022 1162 1.09 1114 1228 1.24 1186 1303 1.40

1339 1343 1.60 1530

1600

1087 1.01 1001 1123 1.05 1073 1156 1.13 1150 1185 1.20 1226 1250 1.35 1291 1319 1.51

1444 1382 1.68 1607

1700

1114 1.07 1108 1151 1.15 1185 1183 1.23 1262 1215 1.31 1339 1276 1.48 1415 1334 1.64

1569 1398 1.80 1722

1800

1141 1.17 1221 1178 1.26 1318 1211 1.35 1390 1243 1.43 1461 1303 1.61 1540 1359 1.78

1702 1418 1.95 1865

1900

1168 1.28 1371 1204 1.37 1502 1238 1.47 1548 1271 1.56 1594 1330 1.74 1664 1386 1.93

1846 1439 2.11 2018

2000

1197 1.39 1485 1231 1.48 1604 1265 1.59 1666 1298 1.69 1727 1358 1.89 1808 1413 2.08

1989 1466 2.27 2171

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor
*Motor drive range is 835 to 1185 rpm. All other rpms require a field-

supplied drive.

NOTES:
1. Boldface indicates field-supplied motor and drive are required.
2. Values include losses for filters, unit casing, and wet coils. See

page 52 for accessory/FIOP static pressure information.

3. Maximum continuous bhp is 1.00 and the maximum continuous

watts are 1000. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confi-
dence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected. See Evaporator-Fan Motor Performance
table on page 55 for additional information.

4. Use of a field-supplied motor may affect wire sizing. Contact your

local representative for details.

5. Interpolation is permissible. Do not extrapolate.

40