PERFORMANCE DATA (cont)

FAN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont)

580D150 (12

1

2

TONS)*

Airflow

(Cfm)

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3750

737

1.41

1300

798

1.64

1486

854

1.84

1658

909

2.12

1893

961

2.35

2097

1014

2.61

2325

3800

745

1.46

1340

805

1.69

1531

861

1.89

1700

915

2.17

1940

967

2.41

2149

1019

2.67

2378

3900

761

1.56

1423

820

1.80

1624

875

2.01

1802

928

2.29

2044

979

2.55

2272

1029

2.80

2494

4000

777

1.67

1514

836

1.92

1725

889

2.14

1914

941

2.40

2140

991

2.68

2387

1040

2.94

2620

4100

793

1.79

1615

851

2.05

1836

904

2.27

2027

955

2.52

2246

1004

2.82

2512

1052

3.08

2746

4200

810

1.91

1717

867

2.18

1948

918

2.41

2149

968

2.65

2361

1017

2.96

2638

1064

3.23

2882

4300

826

2.04

1828

883

2.32

2070

933

2.55

2272

982

2.79

2485

1030

3.11

2773

1076

3.40

3037

4400

842

2.17

1940

898

2.46

2193

948

2.70

2405

996

2.93

2611

1043

3.25

2901

1088

3.56

3184

4500

859

2.31

2061

914

2.60

2316

962

2.85

2539

1010

3.09

2755

1056

3.40

3037

1101

3.73

3341

4600

876

2.45

2184

930

2.76

2459

977

3.01

2683

1024

3.26

2910

1070

3.55

3175

1114

3.90

3498

4700

892

2.60

2316

945

2.91

2593

992

3.18

2837

1039

3.43

3065

1083

3.71

3322

1126

4.07

3655

4800

909

2.77

2468

961

3.07

2737

1008

3.36

3001

1053

3.61

3230

1097

3.88

3479

1140

4.25

3822

4900

926

2.93

2611

977

3.24

2891

1024

3.54

3166

1068

3.80

3405

1111

4.06

3646

1153

4.41

3971

5000

942

3.11

2773

993

3.41

3047

1039

3.73

3341

1080

3.99

3581

1125

4.25

3822

1166

4.59

4139

5100

959

3.29

2937

1009

3.60

3221

1055

3.92

3516

1097

4.19

3767

1139

4.46

4018

1180

4.78

4316

5200

976

3.47

3101

1025

3.78

3387

1071

4.12

3702

1112

4.40

3962

1153

4.67

4214

1194

4.98

4503

5300

993

3.67

3285

1041

3.98

3572

1086

4.33

3897

1127

4.61

4158

1168

4.90

4428

1208

5.19

4698

5400

1010

3.87

3470

1057

4.18

3757

1102

4.54

4093

1142

4.84

4372

1182

5.13

4642

5500

1027

4.07

3655

1073

4.39

3953

1118

4.76

4298

1157

5.07

4586

5600

1043

4.29

3860

1090

4.61

4158

1133

4.99

4512

5700

1060

4.51

4065

1106

4.83

4363

1149

5.22

4726

5800

1077

4.74

4279

1122

5.07

4586

5900

1094

4.98

4503

6000

1111

5.22

4726

6100

6250

580D150 (12

1

2

TONS)* (cont)

Airflow

(Cfm)

External Static Pressure (in. wg)

1.4

1.6

1.8

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3750

1065

2.87

2557

1113

3.12

2783

1158

3.36

2997

1197

3.56

3180

3800

1070

2.94

2620

1118

3.19

2846

1163

3.44

3074

1203

3.65

3267

3900

1079

3.07

2737

1128

3.34

2983

1173

3.60

3221

1214

3.83

3433

4000

1089

3.22

2873

1137

3.49

3120

1183

3.76

3368

1225

4.00

3590

4100

1100

3.36

3001

1147

3.65

3267

1193

3,93

3525

1236

4.19

3767

4200

1110

3.51

3138

1157

3.81

3414

1202

4.09

3674

1245

4.38

3943

4300

1121

3.67

3285

1167

3.97

3562

1212

4.27

3841

1255

4.56

4111

4400

1133

3.84

3442

1178

4.14

3720

1222

4.44

3999

1265

4.74

4279

4500

1144

4.00

3590

1188

4.31

3878

1232

4.62

4167

1274

4.93

4456

4600

1157

4.19

3767

1199

4.49

4046

1242

4.81

4344

1284

5.13

4642

4700

1169

4.38

3943

1210

4.68

4223

1252

5.00

4521

4800

1181

4.58

4130

1222

4.87

4400

1263

5.20

4707

4900

1194

4.77

4307

1234

5.09

4605

5000

1207

4.97

4493

5100

1220

5.18

4689

5200

5300

5400

5500

5600

5700

5800

5900

6000

6100

6250

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor
*Standard motor drive range is 860 to 1080 rpm. Alternate motor drive

range is 900 to 1260 rpm. All other rpms require a field-supplied drive.

NOTES:
1. Boldface indicates field-supplied motor and drive are required.
2. Values include losses for filters, unit casing, and wet coils. See

page 52 for accessory/FIOP static pressure information.

3. Maximum continuous bhp is 4.20 for the standard motor and 5.25 for

the alternate motor. Maximum continuous watts are 3775 for the
standard motor and 4400 for the alternate motor. Extensive motor
and electrical testing on these units ensures that the full range of the
motor can be utilized with confidence. Using your fan motors up to
the wattage ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected. See
Evaporator-Fan Motor Performance table on page 55 for additional
information.

4. Use of a field-supplied motor may affect wire sizing. Contact your

local representative for details.

5. Interpolation is permissible. Do not extrapolate.

38