Fan rpm motor pulley settings, Altitude compensation, 131 performance data (cont) – Bryant 581C User Manual

Page 131

Advertising
background image

131

PERFORMANCE DATA (cont)

FAN RPM AT MOTOR PULLEY SETTING WITH STANDARD MOTOR* — 581B036-150

*Approximate fan rpm shown (standard motor/drive).

FAN RPM AT MOTOR PULLEY SETTING WITH HIGH-STATIC MOTOR* — 581B036-150

*Approximate fan rpm shown (high-static motor/drive).

ALTITUDE COMPENSATION* — 581B036-072

*As the height above sea level increases, there is less oxygen per cubic

foot of air. Therefore, the input rate should be reduced at higher altitudes.

†Orifices are available through your local Bryant distributor.

ALTITUDE COMPENSATION* — 581B090-150

*As the height above sea level increases, there is less oxygen per cubic

foot of air. Therefore, the input rate should be reduced at higher altitudes.

†Orifices are available through your local Bryant distributor.

ALTITUDE DERATING FACTOR*

*Derating of the unit is not required unless the heating value of the gas

exceeds the values listed in the table above, or if the elevation exceeds
6000 ft. Derating conditions must be 4% per thousand ft above 2000 ft.
For example, at 4000 ft, if the heating value of the gas exceeds 1000 Btu/
ft

3

, the unit will require a 16% derating. For elevations above 6000 ft, the

same formula applies. For example, at 7000 ft, the unit will require a 28%
derating of the maximum heating value per the National Fuel Gas Code.

IMPORTANT: Local utility companies may be reducing heat content of gas
at altitudes above 2000 ft. If this is being done, changing spuds may not be
required.

UNIT
581B

MOTOR PULLEY TURNS OPEN

0

1

/

2

1

1

1

/

2

2

2

1

/

2

3

3

1

/

2

4

4

1

/

2

5

5

1

/

2

6

036

1044

1008

971

935

898

862

826

789

753

716

680

048

1185

1144

1102

1061

1019

978

936

895

853

812

770

060

1460

1425

1389

1354

1318

1283

1248

1212

1177

1141

1106

1070

1035

072

1585

1538

1492

1445

1399

1352

1305

1259

1212

1166

1119

090,102

1085

1060

1035

1010

985

960

935

910

890

865

840

120

1080

1060

1035

1015

990

970

950

925

905

880

860

150

1130

1112

1087

1062

1037

1212

987

962

937

912

887

962

830

UNIT
581B

MOTOR PULLEY TURNS OPEN

0

1

/

2

1

1

1

/

2

2

2

1

/

2

3

3

1

/

2

4

4

1

/

2

5

5

1

/

2

6

036

1455

1423

1392

1360

1328

1297

1265

1233

1202

1170

1138

1107

1075

048

1455

1423

1392

1360

1328

1297

1265

1233

1202

1170

1138

1107

1075

060

1685

1589

1557

1525

1493

1460

1428

1396

1364

1332

1300

072

1685

1589

1557

1525

1493

1460

1428

1396

1364

1332

1300

090

1080

1025

1007

988

970

952

933

915

897

878

860

102

1080

1025

1007

988

970

952

933

915

897

878

860

120

1130

1112

1087

1062

1037

1212

987

962

937

912

887

962

830

ELEVATION

(ft)

72,000 AND 115,000/

60,000 and 90,000 BTUH

NOMINAL INPUT

150,000/120,000 BTUH

NOMINAL INPUT

Natural Gas

Orifice Size†

Liquid

Propane

Orifice Size†

Natural

Gas

Orifice Size

Liquid

Propane

Orifice Size†

0-2,000

33/38

43

30/32

38

2,000

34/39

43

30/33

39

3,000

35/40

44

31/34

40

4,000

36/41

44

32/35

41

5,000

36/41

44

33/35

42

6,000

37/42

45

34/36

43

7,000

37/42

45

35/37

43

8,000

38/43

46

36/37

44

9,000

39/43

47

37/38

44

10,000

41/44

48

38/40

45

11,000

43/45

48

39/41

45

12,000

44/45

49

40/42

46

13,000

44/46

49

41/43

47

14,000

45/47

50

42/43

47

ELEVATION

(ft)

125,000, 180,000, AND

224,000 BTUH

NOMINAL INPUT

250,000 BTUH

NOMINAL INPUT

Natural Gas

Orifice

Size†

Liquid

Propane

Orifice Size†

Natural Gas

Orifice

Size†

Liquid

Propane

Orifice Size†

0-2,000

31

41

30

38

2,000

32

42

30

39

3,000

32

42

31

40

4,000

32

42

32

41

5,000

33

43

33

42

6,000

34

43

34

43

7,000

35

44

35

43

8,000

36

44

36

44

9,000

37

45

37

44

10,000

38

46

38

45

11,000

39

47

39

45

12,000

40

47

40

46

13,000

41

48

41

47

14,000

42

48

42

47

ELEVATION

MAXIMUM HEATING VALUE (Btu/ft

3

)

0-2000

1100

2001-3000

1050

3001-4000

1000

4001-5000

950

5001-6000

900

5

81B0

36-

15
0

Advertising