Fan rpm at motor pulley settings, Evaporator fan motor performance – Bryant 581C User Manual

Page 161

Advertising
background image

161

PERFORMANCE DATA — 581C

FAN RPM AT MOTOR PULLEY SETTING WITH STANDARD MOTOR* — 581C024-060

*Approximate fan rpm shown (standard motor/drive).

FAN RPM AT MOTOR PULLEY SETTING WITH HIGH-STATIC MOTOR* — 581C030-060

*Approximate fan rpm shown (high-static motor/drive).

EVAPORATOR-FAN MOTOR PERFORMANCE — STANDARD MOTOR — 581C024-060

LEGEND

Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the

motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will not
result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

EVAPORATOR-FAN MOTOR PERFORMANCE — HIGH-STATIC MOTORS — 581C036-060

LEGEND

Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the

motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will not
result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

UNIT
581C

MOTOR PULLEY TURNS OPEN

0

1

/

2

1

1

1

/

2

2

2

1

/

2

3

3

1

/

2

4

4

1

/

2

5

5

1

/

2

6

024

936

906

876

846

816

786

756

726

696

656

639

036

1044

1008

971

935

898

862

826

789

753

716

680

048

1185

1144

1102

1061

1019

978

936

895

853

812

770

060

1460

1425

1389

1354

1318

1283

1248

1212

1177

1141

1106

1070

1035

UNIT
581C

MOTOR PULLEY TURNS OPEN

0

1

/

2

1

1

1

/

2

2

2

1

/

2

3

3

1

/

2

4

4

1

/

2

5

5

1

/

2

6

030

1455

1423

1392

1360

1328

1297

1265

1233

1202

1170

1138

1107

1075

048

1455

1423

1392

1360

1328

1297

1265

1233

1202

1170

1138

1107

1075

060

1685

1589

1557

1525

1493

1460

1428

1396

1364

1332

1300

UNIT
581C

UNIT

PHASE

MAXIMUM

CONTINUOUS BHP*

MAXIMUM

OPERATING WATTS*

UNIT VOLTAGE

MAXIMUM

AMP DRAW

024

Single

0.58

580

208/230

2.0

036

Single

1.20

1000

208/230

4.9

Three

1.20

1000

208/230

4.9

460

2.2

575

2.2

048

Single

1.20

1000

208/230

4.9

Three

1.20

1000

208/230

4.9

460

2.2

575

2.2

060

Single

1.30

1650

208/230

9.2

Three

2.40

2120

208/230

6.7

460

3.0

575

3.0

UNIT
581C

UNIT

PHASE

MAXIMUM

CONTINUOUS BHP*

MAXIMUM

OPERATING WATTS*

UNIT VOLTAGE

MAXIMUM

AMP DRAW

036

Three

2.40

2120

208/230

6.7

460

3.0

575

3.0

048

Three

2.40

2120

208/230

6.7

460

3.0

575

3.0

060

Three

2.90

2615

208/230

8.6

460

3.9

575

3.9

Advertising